| Plan Review Notes For Permit 06101053 |
| Permit Number |
06101053 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-01 12:27:40 | *****DENIED***** | | | | | | | | | | | | 1.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY | | | THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING NORTH | | | DIXIE HIGHWAY.AS PER WEST PALM BEACH CODE, THOSE | | | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN | | | WIDTH. INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN | | | 3" IN HEIGHT. | | | | | | 2.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE | | | BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | SPRINKLER SYSTEM. | | | | | | 4. FIRE SPRINKLER SYSTEM SHALL BE MONITORED. | | | | | | 5. SHOW DETAIL OF THE FIRE DEPARTMENT CONNECTION (FDC). | | | THE FDC SHALL BE NO GREATER THAN 150 FEET TO THE | | | NEAREST FIRE HYDRANT. | | | | | | 6.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE | | | DEPARTMENT CONNECTIONS. | | | | | | 7.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY | | | LIGHTING, AND FIRE EXTINGUISHERS (2A-10 BC RATED) FOR | | | THE GROUND FLOOR PLAN. | | | | | | 8.WILL THIS BUILDING HAVE A FIRE ALARM SYSTEM? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|