2006-12-01 12:27:40*****DENIED*****
  
  
  
 1.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY
 THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING NORTH
 DIXIE HIGHWAY.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN
 WIDTH. INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN
 3" IN HEIGHT.
  
 2.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 SPRINKLER SYSTEM.
  
 4. FIRE SPRINKLER SYSTEM SHALL BE MONITORED.
  
 5. SHOW DETAIL OF THE FIRE DEPARTMENT CONNECTION (FDC).
 THE FDC SHALL BE NO GREATER THAN 150 FEET TO THE
 NEAREST FIRE HYDRANT.
  
 6.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
 7.INDICATE THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTING, AND FIRE EXTINGUISHERS (2A-10 BC RATED) FOR
 THE GROUND FLOOR PLAN.
  
 8.WILL THIS BUILDING HAVE A FIRE ALARM SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  