| 2006-11-26 12:27:58 | MERRY PLACE |
| | |
| | 1713 N DIXIE HWY TYPE IV BLDG. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME |
| | NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME |
| | ADDITIONAL INFORMATION. |
| | |
| | ********** UNSAT ************* |
| | |
| | 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR |
| | THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE |
| | DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER |
| | ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON |
| | SAID CIRCUIT. |
| | MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS |
| | AS NOTED IN CODES ABOVE. |
| | PLEASE SEE THAT A DESIGNATED AREA AND THE LIKE SHALL BE |
| | INDICATED. |
| | |
| | 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING |
| | CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE |
| | LOCATED ON PLANS AND IS REQUIRED. |
| | |
| | 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE |
| | ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3, |
| | 230.42 ETC |
| | PLEASE SEE THE LIGHTING LOADS AS SHOWN DO NOT CORRELATE |
| | WITH THE NUMBER OF FIXTURES ON PLANS OR THE WATTAGE ON |
| | THE FIXTURE SCHEDULE. THE LOADS BEING SHOWN FOR |
| | INSTANCE FOR THE EXTERIOR LIGHTS IS LISTED AT 100 |
| | WATTS, HOWEVER AS THE FIXTURE TYPE ON PLANS SHOWS FIVE |
| | F-1 FIXTURES WHICH ARE 100 WATTS EACH THOSE ALONG |
| | EXCEED THE LOAD AS SHOWN ON PANEL SCHEDULE FOR THIS |
| | CIRCUIT. PLEASE ALSO THE LOADS FOR THE OTHER EXTERIOR |
| | FIXTURES WHICH WERE ALSO NOT ADDED. |
| | PLEASE SEE ALL INTERIOR LIGHTS AS THE SAME SCENARIO |
| | TAKES PLACE. THE AMOUNT OF WATTAGE BASED ON THE |
| | FIXTURES SHOWN ON THE FIXTURE SCHEDULE AND PLANS DO NOT |
| | CORRELATE. |
| | PLEASE SEE THE FOLLOWING COMMENTS ALSO AS THE EM/EXT |
| | LIGHTS ARE NOT CIRCUITED. |
| | |
| | 4) NOTE: PLEASE INDICATE CIRCUITING FOR THE EM/EXT |
| | LIGHTS AS REQUIRED PER 700.12E. PLEASE SEE NOTE #3 |
| | ABOVE FOR LOADS. |
| | |
| | 5) NOTE: PLEASE MISSING RECEPTACLE FOR 2FT OF WALL |
| | SPACE IN UNIT PER 210.52 |
| | |
| | 6) NOTE: PLEASE SEE 408.7, 240.24 AND 110.26 FOR THE |
| | LOCATION OF THE HOUSE ELECTRICAL PANEL SHOULD NOT BE |
| | LOCATED IN ANY STORAGE AREA AND/OR LOCATION WITH EASILY |
| | IGNITABLE MATERIALS OR FLAMMABLES. |
| | |
| | 7) NOTE: PLEASE PROVIDE CIRCUITING FOR THE EXTERIOR |
| | EMERGENCY LIGHTS. PLEASE KNOW THESE SHALL NOT BE ON THE |
| | LOAD SIDE OF THE TIME CLOCK AS BEING INDICATED FOR |
| | STAIR LIGHTS. WHEN USING A ASTRONOMICAL TIME CLOCK, |
| | THESE SHALL WIRED ON THE LINE SIDE OF SAID TIME CLOCK. |
| | |
| | PLEASE SEE AS A SAFETY DESIGN ISSUE, IF THE STAIRS ARE |
| | ENCLOSED IN ANY FASHION AND CAN EVEN GET DARK ENOUGH IN |
| | THE MIDDLE OF THE DAY DUE TO OVER CAST OF DENSE CLOUDS, |
| | A PHOTO-CELL FOR CONTROL IN PLACE OF OR WIRED INLINE ON |
| | THE LOAD SIDE OF THE TIME CLOCK WOULD ENSURE THE |
| | MINIMUM FOOT CANDLES FOR STAIR WAYS AT ALL TIMES. |
| | PLEASE SEE LS 101 7.8.1.3,7.9.2.2 |
| | |
| | 8) NOTE: PLEASE SEE THE ELECTRICAL J-BOX FOR THE |
| | CONNECTION OF THE GAS HOT WATER HEATER IS BEING SHOWN |
| | LOCATED IN THE STAIRWAY LOCATION? PLEASE CLARIFY THIS. |
| | WHERE IS THE GAS WATER HEATER GOING TO BE INSTALLED? |
| | MAY NOT INTERFERE WITH MEANS OF EGRESS IN ANY WAY. |
| | |
| | 9) NOTE: PLEASE SEE METER CENTER FOR THIS BUILDING TYPE |
| | SEEMS TO INDICATE BEING 400A RATED AND THE SERVICE |
| | ENTRANCE CONDUCTORS ARE ONLY RATED FOR 350A'S PER |
| | 310.15B6. PLEASE EITHER INSTALL A MAIN BREAKER IN THE |
| | MC WHICH WILL LIMIT THE LOAD ON THE CONDUCTORS TO |
| | 350A'S OR ADJUST THE CONDUCTORS FOR THE 400A SERVICE |
| | PROVIDED. |
| | PLEASE KNOW IF ADJUSTING THE SEC'S AND INCREASING THE |
| | SIZE TO 400 MCM, THEN PLEASE SEE 250.66 FOR THE SIZING |
| | OF THE GROUNDING ELECTRODE CONDUCTOR WHICH WILL BE |
| | REQUIRED TO BE INCREASED TO A 1/0. 310.15B6, 250.66, |
| | 240.4, 240.6 |
| | |
| | 10) NOTE: PLEASE SEE E311 AS THE RATINGS FOR EQUIPMENT |
| | IS BEING NOTED AND BASED ON A MAIN RATING WITH SERIES |
| | RATED EQUIPMENT. |
| | PLEASE SEE SOME BUILDING TYPES WHICH ARE SHOWN AS BEING |
| | MLO?? HOW WILL THE RATINGS BE AFFECTED THEN? |
| | PLEASE SEE 110.9, AND 240.12 FOR COORDINATION REQUIRED |
| | |
| | |
| | 11) NOTE: PLEASE SEE THE TOTAL SQ FT ON THE PERMIT |
| | APPLICATION SHOWS 1282 SQ FT, HOWEVER BASED ON PLANS |
| | THIS DOES NOT CORRELATE WITH THIS TYPE IV BUILDING. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |