2006-11-26 12:27:58MERRY PLACE
  
 1713 N DIXIE HWY TYPE IV BLDG.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME
 ADDITIONAL INFORMATION.
  
 ********** UNSAT *************
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR
 THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE
 DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER
 ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON
 SAID CIRCUIT.
 MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS
 AS NOTED IN CODES ABOVE.
 PLEASE SEE THAT A DESIGNATED AREA AND THE LIKE SHALL BE
 INDICATED.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING
 CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE
 LOCATED ON PLANS AND IS REQUIRED.
  
 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE
 ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3,
 230.42 ETC
 PLEASE SEE THE LIGHTING LOADS AS SHOWN DO NOT CORRELATE
 WITH THE NUMBER OF FIXTURES ON PLANS OR THE WATTAGE ON
 THE FIXTURE SCHEDULE. THE LOADS BEING SHOWN FOR
 INSTANCE FOR THE EXTERIOR LIGHTS IS LISTED AT 100
 WATTS, HOWEVER AS THE FIXTURE TYPE ON PLANS SHOWS FIVE
 F-1 FIXTURES WHICH ARE 100 WATTS EACH THOSE ALONG
 EXCEED THE LOAD AS SHOWN ON PANEL SCHEDULE FOR THIS
 CIRCUIT. PLEASE ALSO THE LOADS FOR THE OTHER EXTERIOR
 FIXTURES WHICH WERE ALSO NOT ADDED.
 PLEASE SEE ALL INTERIOR LIGHTS AS THE SAME SCENARIO
 TAKES PLACE. THE AMOUNT OF WATTAGE BASED ON THE
 FIXTURES SHOWN ON THE FIXTURE SCHEDULE AND PLANS DO NOT
 CORRELATE.
 PLEASE SEE THE FOLLOWING COMMENTS ALSO AS THE EM/EXT
 LIGHTS ARE NOT CIRCUITED.
  
 4) NOTE: PLEASE INDICATE CIRCUITING FOR THE EM/EXT
 LIGHTS AS REQUIRED PER 700.12E. PLEASE SEE NOTE #3
 ABOVE FOR LOADS.
  
 5) NOTE: PLEASE MISSING RECEPTACLE FOR 2FT OF WALL
 SPACE IN UNIT PER 210.52
  
 6) NOTE: PLEASE SEE 408.7, 240.24 AND 110.26 FOR THE
 LOCATION OF THE HOUSE ELECTRICAL PANEL SHOULD NOT BE
 LOCATED IN ANY STORAGE AREA AND/OR LOCATION WITH EASILY
 IGNITABLE MATERIALS OR FLAMMABLES.
  
 7) NOTE: PLEASE PROVIDE CIRCUITING FOR THE EXTERIOR
 EMERGENCY LIGHTS. PLEASE KNOW THESE SHALL NOT BE ON THE
 LOAD SIDE OF THE TIME CLOCK AS BEING INDICATED FOR
 STAIR LIGHTS. WHEN USING A ASTRONOMICAL TIME CLOCK,
 THESE SHALL WIRED ON THE LINE SIDE OF SAID TIME CLOCK.
  
 PLEASE SEE AS A SAFETY DESIGN ISSUE, IF THE STAIRS ARE
 ENCLOSED IN ANY FASHION AND CAN EVEN GET DARK ENOUGH IN
 THE MIDDLE OF THE DAY DUE TO OVER CAST OF DENSE CLOUDS,
 A PHOTO-CELL FOR CONTROL IN PLACE OF OR WIRED INLINE ON
 THE LOAD SIDE OF THE TIME CLOCK WOULD ENSURE THE
 MINIMUM FOOT CANDLES FOR STAIR WAYS AT ALL TIMES.
 PLEASE SEE LS 101 7.8.1.3,7.9.2.2
  
 8) NOTE: PLEASE SEE THE ELECTRICAL J-BOX FOR THE
 CONNECTION OF THE GAS HOT WATER HEATER IS BEING SHOWN
 LOCATED IN THE STAIRWAY LOCATION? PLEASE CLARIFY THIS.
 WHERE IS THE GAS WATER HEATER GOING TO BE INSTALLED?
 MAY NOT INTERFERE WITH MEANS OF EGRESS IN ANY WAY.
  
 9) NOTE: PLEASE SEE METER CENTER FOR THIS BUILDING TYPE
 SEEMS TO INDICATE BEING 400A RATED AND THE SERVICE
 ENTRANCE CONDUCTORS ARE ONLY RATED FOR 350A'S PER
 310.15B6. PLEASE EITHER INSTALL A MAIN BREAKER IN THE
 MC WHICH WILL LIMIT THE LOAD ON THE CONDUCTORS TO
 350A'S OR ADJUST THE CONDUCTORS FOR THE 400A SERVICE
 PROVIDED.
 PLEASE KNOW IF ADJUSTING THE SEC'S AND INCREASING THE
 SIZE TO 400 MCM, THEN PLEASE SEE 250.66 FOR THE SIZING
 OF THE GROUNDING ELECTRODE CONDUCTOR WHICH WILL BE
 REQUIRED TO BE INCREASED TO A 1/0. 310.15B6, 250.66,
 240.4, 240.6
  
 10) NOTE: PLEASE SEE E311 AS THE RATINGS FOR EQUIPMENT
 IS BEING NOTED AND BASED ON A MAIN RATING WITH SERIES
 RATED EQUIPMENT.
 PLEASE SEE SOME BUILDING TYPES WHICH ARE SHOWN AS BEING
 MLO?? HOW WILL THE RATINGS BE AFFECTED THEN?
 PLEASE SEE 110.9, AND 240.12 FOR COORDINATION REQUIRED
  
  
 11) NOTE: PLEASE SEE THE TOTAL SQ FT ON THE PERMIT
 APPLICATION SHOWS 1282 SQ FT, HOWEVER BASED ON PLANS
 THIS DOES NOT CORRELATE WITH THIS TYPE IV BUILDING.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW