Notes
Date Text
2006-12-06 11:47:44BUILDING REVIEW CHECKLIST:
 1- NOTICE OF COMMENCEMENT AND IMPACT FEES STAMPED
 DRAWINGS AND PAID RECEIPTS WILL BE SUBMITTED LATER.
  
 2- REVISE ENERGY CALCULATIONS:
 A) CALCULATIONS NEED TO BE PERFORMED FOR THE WHOLE
 BUILDING, NOT FOR EACH UNIT. SEC. 13-600.0 METHOD A OF
 2004 FBC.
 B) NAME AND LICENSE # OF ENGINEER AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
 C) PROVIDE COMPLETE INFORMATION FOR ITEM #8, FLOOR
 TYPES.
 D) INSULATION R VALUE SPECIFIED IN PROJECT MANUAL
 SPECS SEC. 07200 TO MATCH ENERGY CALCULATIONS.
 E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED
 ADDRESS AND BUILDER NAME.
 F) OWNER/AGENT TO SIGN AND DATE ALL ENERGY FORMS.
 NOTE: THIS APPLIES TO ALL ENERGY FORMS FOR ALL
 BUILDINGS. CHECK ALL ENERGY FORMS TO BE SUBMITTED.
  
 3- NEED SIGNED AND SEALED SURVEYS SHOWING EXACT
 LOCATIONS OF BUILDINGS IN RELATIONSHIP WITH THE
 PROPERTY LINES AND OTHER BUILDINGS TO VERIFY COMPLIANCE
 WITH TABLES601, 602 FOR FIRE RESISTANCE AND TABLE
 704.8 FBC 2004 FOR OPENINGS ALLOWED.PROVIDE ALL
 DISTANCES BETWEEN BUILDINGS AND PROPERTY LINES AND MAKE
 SURE ALL BUILDINGS HAVE THE DIMENSIONS BETWEEN BUILDING
 SEPARATION FOR BUILDINGS ON SAME LOT. IF BUILDINGS ARE
 ON SAME LOT, THEN SPECIFY THE PROPOSED PROPERTY LINE
 BETWEEN THEM.BUILDINGS WITH IRREGULAR SHAPES NEED TO
 SHOW DIMENSIONS WITH CLOSEST DISTANCE TO ADJACENT
 BUILDINGS. EG: SOME BUILDINGS HAVE SETBACKS IN THE
 FOOTPRINT. MAKE SURE DISTANCES PROVIDED INCLUDE THE
 CLOSEST DISTANCE BETWEEN BUILDINGS. SITE PLAN SUBMITTED
 DOESN'T PROVIDE ALL THIS INFORMATION.
  
 4- SHEET A004:
 A) OCCUPANCY LOAD CALCULATIONS NEED TO BE
 ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN
 ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3.
 ACCORDING TO THIS SECTION,TABLE 1004.1.2 FBC 2004 AND
 FLOOR PLANS, THE FLOOR AREA PER OCCUPANT SHALL BE
 CALCULATED FOR 5S.F. PER PERSON. REVISE OCCUPANT LOAD
 CALCULATIONS AS REQUIRED.
  
 B) MISSING UNIT MODEL TYPE IN PROJECT TABULATION
 CHART.
 C) BUILDING AND UNIT AREAS DON'T MATCH. SEE SHEET
 A004 AND SHEETS A202 AND A304.REVISE AS REQUIRED.
 NEED CORRECT AREAS TO ESTIMATE BUILDING VALUATION. SEC.
 108.3 CITY AMENDMENTS TO FBC 2004. PROVIDE PORCHES,
 BALCONIES AND BUILDING AREAS.
  
 5- SHEET A101:
 A) SPECIFY NUMBER OF PARKING SPACES REQUIRED BY
 ZONING FOR BUILDING C3 TO VERIFY COMPLIANCE OF
 HANDICAPPED SPACES PROVIDED AS REQUIRED BY CHAPTER 11
 FBC 2004.
  
 B) PROVIDE DRAWINGS SHOWING PARKING SIZES AND
 ACCESSIBLE ROUTEFROM PARKING SPACE TO PUBLIC ASSEMBLY
 BUILDING C3TO VERIFY COMPLIANCE WITH CHAPTER 11 FBC
 2004.
  
 6- OWNER TO PROVIDE LETTER CERTIFYING THAT NO FEDERAL
 MONIES ARE USED FOR THIS PROJECT. OTHERWISE,PROJECT
 NEEDS TO BE REVIEWED FOR SECTION 504 OF THE
 REHABILITATION ACT COMPLIANCE.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SINGLE HUNG WINDOW. NOA 01-0629.08 IS EXPIRED.
 ALSO, NEED FLORIDA PRODUCT APPROVAL COVER PAGE. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING COVER
 PAGE. FLORIDA PRODUCT APPROVAL COVER PAGE APPLIES TO
 ALL PRODUCT APPROVALS. IF THERE IS NO FLORIDA PRODUCT
 APPROVAL, THEN SUBMIT THE DADE COUNTY NOA ONLY.
  
 B) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 C) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING SPECIFIC CONNECTOR.
  
 D) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLYU905.
  
 E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 F) FIXED WINDOWS: NEED PRODUCT APPROVAL FOR LARGE
 MISSILE IMPACT AS REQUIRED BY SEC. 1609.1.4. NOA
 02-0123.03 IS FOR SMALL MISSILE IMPACT RESISTANT
 WINDOWS. ALSO, PROVIDE FLORIDA COVER PAGE.
  
 G) ALUMINUM TUBE MULLIONS: NEED PRODUCT APPROVAL FOR
 LARGE MISSILE IMPACT. NOA 02-0501.04 SUBMITTED HAS NOT
 RATING FOR MISSILE IMPACT. ALSO, PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 ***NOTE: FROM SUBMITTED NOA SPECIFY SPECIFIC FASTENING
 METHOD TO VERIFY COMPLIANCE WITH SEC. 1609 FBC 2004.
  
 H) ALUMINUM STOREFRONT WINDOWS: PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 I) LEASING/RES. SVC ENTRY DOORS: PROVIDE FLORIDA
 PRODUCT APPROVAL COVER PAGE.
  
 J) FLAT ROOF: PROVIDE FLAT ROOF CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS PER RAS
 117 AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE
 OF NOA.
 PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE.NOTE:
 THIS APPLIES TO ALL PRODUCT APPROVALS.
 PROVIDE ONLY THE PAGES WITH THE APPROVED ASSEMBLY TO BE
 INSTALLED ALONG WITH ALL THE FRONT PAGES SHOWING ALL
 APPROVED COMPONENTS AND LAST PAGE WITH THE GENERAL
 LIMITATIONS.
  
  
 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 11- SHEET A103:
 A) REVISE DETAIL 19 TO MATCH DETAIL 7/700.1. SHELVES
 HEIGHT 48" MAX.
  
 B) PROVIDE DETAILS/SPECS FOR GRAB BARS
 REINFORCEMENT. MATERIAL AND INSTALLATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 12- SHEET A104:
 A) CLARIFY COMMON USE FACILITIES NOTE # 2A. WHAT'S
 THE QUESTION MARK FOR?.
 B) REVISE RESTROOMS NOTE # 5C. SEE FIGURE 30 ON
 CHAPTER 11 FBC 2004.
  
 13- SHEET 110:
 A) DETAIL 20: CLARIFY QUESTION MARKS ON CONCRETE
 BLOCK THICKNESS.
 B) UPDATE ASSEMBLY AND PENETRATIONS SCHEDULE.
 REFERENCE UL 2004, NOT UL 1999.
  
 14- SHEET A202:CLARIFY SQUARE FOOTAGES.ALSO,
 COORDINATE ALL THESE AREAS WITH GENERAL AREA TABULATION
 ON SHEET A004.
  
 15- SHEET A304: SEE PLUMBING COMMENTS AND SEC. 1611 FBC
 2004..
  
 16- SHEET A400: DOESN'T APPLY TO THIS BUILDING.
  
 17- SHEET A500: PROVIDE ONLY INFORMATION THAT
 CORRESPONDS TO THIS BUILDING.
  
 18- SHEETA701.1:DETAIL 01: HOW IS THE FASTENER
 EMBEDED 1-1/4" INTO THE BUCK IF THE BUCK IS ONLY 1X
 THICK. REVISE AS REQUIRED.
  
 19- SHEET A703: WOOD IN CONTACT WITH CONCRETE BLOCK TO
 BE PRESSURE TREATED. REVISE DETAILSAS REQUIRED.
  
 20- SHEET A704: PROVIDE ONLY THE DETAILS THAT APPLY TO
 THIS BUILDING.
  
 21- SHEET A705: PROVIDE ONLY THE DETAILS THAT APPLY TO
 THIS BUILDING.
  
 22- SHEET A706.1: PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS BUILDING.
  
 23- SHEET A706.2: PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS BUILDING.
  
 24- SHEET A707: PROVIDE ONLY THE DETAILS THAT APPLY TO
 THIS BUILDING.
  
 25- SHEET A810:
 A) SEE COMMENTS ONSHEET A004 REGARDING OCCUPANT
 LOAD.
 B) SEE PLUMBING COMMENTS REGARDING PROPER FACILITY
 USE.FINAL FLOOR LAYOUTMAY AFFECT CALCULATIONS ON
 SHEET A004 AS WELL.
 C) MULTIPURPOSE ROOM AND COUNSELING AREA MAY BE
 COMBINED ALSO. TAKE THIS IN CONSIDERATION WHEN DOING
 OCCUPANT LOAD CALCULATIONS.
 D) NUMBER OF PEOPLE MAY AFFECT NUMBER OF EGRESS
 DOORS REQUIRED.
  
 26- SHEET S-2: TRUSS TIE DOWN SCHEDULE. REVISE NOTE #6
 FOR CONNECTOR C (SIMPSON MGT). NEED 12" EMBEDMENT. SEE
 SIMPSON CATALOGUE.
  
 27- PROVIDE COMPLETE DETAILS AND SPECS FOR INSTALLATION
 OF RECESSED GAS WATER HEATER. PROVIDE DETAILS AND SPECS
 FOR WALL SEPARATING WATER HEATER AND AIR HANDLER UNIT.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER