| 2006-12-06 11:47:44 | BUILDING REVIEW CHECKLIST: |
| | 1- NOTICE OF COMMENCEMENT AND IMPACT FEES STAMPED |
| | DRAWINGS AND PAID RECEIPTS WILL BE SUBMITTED LATER. |
| | |
| | 2- REVISE ENERGY CALCULATIONS: |
| | A) CALCULATIONS NEED TO BE PERFORMED FOR THE WHOLE |
| | BUILDING, NOT FOR EACH UNIT. SEC. 13-600.0 METHOD A OF |
| | 2004 FBC. |
| | B) NAME AND LICENSE # OF ENGINEER AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES. |
| | C) PROVIDE COMPLETE INFORMATION FOR ITEM #8, FLOOR |
| | TYPES. |
| | D) INSULATION R VALUE SPECIFIED IN PROJECT MANUAL |
| | SPECS SEC. 07200 TO MATCH ENERGY CALCULATIONS. |
| | E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED |
| | ADDRESS AND BUILDER NAME. |
| | F) OWNER/AGENT TO SIGN AND DATE ALL ENERGY FORMS. |
| | NOTE: THIS APPLIES TO ALL ENERGY FORMS FOR ALL |
| | BUILDINGS. CHECK ALL ENERGY FORMS TO BE SUBMITTED. |
| | |
| | 3- NEED SIGNED AND SEALED SURVEYS SHOWING EXACT |
| | LOCATIONS OF BUILDINGS IN RELATIONSHIP WITH THE |
| | PROPERTY LINES AND OTHER BUILDINGS TO VERIFY COMPLIANCE |
| | WITH TABLES601, 602 FOR FIRE RESISTANCE AND TABLE |
| | 704.8 FBC 2004 FOR OPENINGS ALLOWED.PROVIDE ALL |
| | DISTANCES BETWEEN BUILDINGS AND PROPERTY LINES AND MAKE |
| | SURE ALL BUILDINGS HAVE THE DIMENSIONS BETWEEN BUILDING |
| | SEPARATION FOR BUILDINGS ON SAME LOT. IF BUILDINGS ARE |
| | ON SAME LOT, THEN SPECIFY THE PROPOSED PROPERTY LINE |
| | BETWEEN THEM.BUILDINGS WITH IRREGULAR SHAPES NEED TO |
| | SHOW DIMENSIONS WITH CLOSEST DISTANCE TO ADJACENT |
| | BUILDINGS. EG: SOME BUILDINGS HAVE SETBACKS IN THE |
| | FOOTPRINT. MAKE SURE DISTANCES PROVIDED INCLUDE THE |
| | CLOSEST DISTANCE BETWEEN BUILDINGS. SITE PLAN SUBMITTED |
| | DOESN'T PROVIDE ALL THIS INFORMATION. |
| | |
| | 4- SHEET A004: |
| | A) OCCUPANCY LOAD CALCULATIONS NEED TO BE |
| | ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN |
| | ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3. |
| | ACCORDING TO THIS SECTION,TABLE 1004.1.2 FBC 2004 AND |
| | FLOOR PLANS, THE FLOOR AREA PER OCCUPANT SHALL BE |
| | CALCULATED FOR 5S.F. PER PERSON. REVISE OCCUPANT LOAD |
| | CALCULATIONS AS REQUIRED. |
| | |
| | B) MISSING UNIT MODEL TYPE IN PROJECT TABULATION |
| | CHART. |
| | C) BUILDING AND UNIT AREAS DON'T MATCH. SEE SHEET |
| | A004 AND SHEETS A202 AND A304.REVISE AS REQUIRED. |
| | NEED CORRECT AREAS TO ESTIMATE BUILDING VALUATION. SEC. |
| | 108.3 CITY AMENDMENTS TO FBC 2004. PROVIDE PORCHES, |
| | BALCONIES AND BUILDING AREAS. |
| | |
| | 5- SHEET A101: |
| | A) SPECIFY NUMBER OF PARKING SPACES REQUIRED BY |
| | ZONING FOR BUILDING C3 TO VERIFY COMPLIANCE OF |
| | HANDICAPPED SPACES PROVIDED AS REQUIRED BY CHAPTER 11 |
| | FBC 2004. |
| | |
| | B) PROVIDE DRAWINGS SHOWING PARKING SIZES AND |
| | ACCESSIBLE ROUTEFROM PARKING SPACE TO PUBLIC ASSEMBLY |
| | BUILDING C3TO VERIFY COMPLIANCE WITH CHAPTER 11 FBC |
| | 2004. |
| | |
| | 6- OWNER TO PROVIDE LETTER CERTIFYING THAT NO FEDERAL |
| | MONIES ARE USED FOR THIS PROJECT. OTHERWISE,PROJECT |
| | NEEDS TO BE REVIEWED FOR SECTION 504 OF THE |
| | REHABILITATION ACT COMPLIANCE. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) SINGLE HUNG WINDOW. NOA 01-0629.08 IS EXPIRED. |
| | ALSO, NEED FLORIDA PRODUCT APPROVAL COVER PAGE. GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING COVER |
| | PAGE. FLORIDA PRODUCT APPROVAL COVER PAGE APPLIES TO |
| | ALL PRODUCT APPROVALS. IF THERE IS NO FLORIDA PRODUCT |
| | APPROVAL, THEN SUBMIT THE DADE COUNTY NOA ONLY. |
| | |
| | B) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR |
| | "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS. |
| | |
| | C) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING SPECIFIC CONNECTOR. |
| | |
| | D) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL |
| | ASSEMBLYU905. |
| | |
| | E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER |
| | HEATER. |
| | |
| | F) FIXED WINDOWS: NEED PRODUCT APPROVAL FOR LARGE |
| | MISSILE IMPACT AS REQUIRED BY SEC. 1609.1.4. NOA |
| | 02-0123.03 IS FOR SMALL MISSILE IMPACT RESISTANT |
| | WINDOWS. ALSO, PROVIDE FLORIDA COVER PAGE. |
| | |
| | G) ALUMINUM TUBE MULLIONS: NEED PRODUCT APPROVAL FOR |
| | LARGE MISSILE IMPACT. NOA 02-0501.04 SUBMITTED HAS NOT |
| | RATING FOR MISSILE IMPACT. ALSO, PROVIDE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE. |
| | |
| | ***NOTE: FROM SUBMITTED NOA SPECIFY SPECIFIC FASTENING |
| | METHOD TO VERIFY COMPLIANCE WITH SEC. 1609 FBC 2004. |
| | |
| | H) ALUMINUM STOREFRONT WINDOWS: PROVIDE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE. |
| | |
| | I) LEASING/RES. SVC ENTRY DOORS: PROVIDE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE. |
| | |
| | J) FLAT ROOF: PROVIDE FLAT ROOF CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS PER RAS |
| | 117 AS REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE |
| | OF NOA. |
| | PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE.NOTE: |
| | THIS APPLIES TO ALL PRODUCT APPROVALS. |
| | PROVIDE ONLY THE PAGES WITH THE APPROVED ASSEMBLY TO BE |
| | INSTALLED ALONG WITH ALL THE FRONT PAGES SHOWING ALL |
| | APPROVED COMPONENTS AND LAST PAGE WITH THE GENERAL |
| | LIMITATIONS. |
| | |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- SHEET A103: |
| | A) REVISE DETAIL 19 TO MATCH DETAIL 7/700.1. SHELVES |
| | HEIGHT 48" MAX. |
| | |
| | B) PROVIDE DETAILS/SPECS FOR GRAB BARS |
| | REINFORCEMENT. MATERIAL AND INSTALLATION. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- SHEET A104: |
| | A) CLARIFY COMMON USE FACILITIES NOTE # 2A. WHAT'S |
| | THE QUESTION MARK FOR?. |
| | B) REVISE RESTROOMS NOTE # 5C. SEE FIGURE 30 ON |
| | CHAPTER 11 FBC 2004. |
| | |
| | 13- SHEET 110: |
| | A) DETAIL 20: CLARIFY QUESTION MARKS ON CONCRETE |
| | BLOCK THICKNESS. |
| | B) UPDATE ASSEMBLY AND PENETRATIONS SCHEDULE. |
| | REFERENCE UL 2004, NOT UL 1999. |
| | |
| | 14- SHEET A202:CLARIFY SQUARE FOOTAGES.ALSO, |
| | COORDINATE ALL THESE AREAS WITH GENERAL AREA TABULATION |
| | ON SHEET A004. |
| | |
| | 15- SHEET A304: SEE PLUMBING COMMENTS AND SEC. 1611 FBC |
| | 2004.. |
| | |
| | 16- SHEET A400: DOESN'T APPLY TO THIS BUILDING. |
| | |
| | 17- SHEET A500: PROVIDE ONLY INFORMATION THAT |
| | CORRESPONDS TO THIS BUILDING. |
| | |
| | 18- SHEETA701.1:DETAIL 01: HOW IS THE FASTENER |
| | EMBEDED 1-1/4" INTO THE BUCK IF THE BUCK IS ONLY 1X |
| | THICK. REVISE AS REQUIRED. |
| | |
| | 19- SHEET A703: WOOD IN CONTACT WITH CONCRETE BLOCK TO |
| | BE PRESSURE TREATED. REVISE DETAILSAS REQUIRED. |
| | |
| | 20- SHEET A704: PROVIDE ONLY THE DETAILS THAT APPLY TO |
| | THIS BUILDING. |
| | |
| | 21- SHEET A705: PROVIDE ONLY THE DETAILS THAT APPLY TO |
| | THIS BUILDING. |
| | |
| | 22- SHEET A706.1: PROVIDE ONLY THE DETAILS THAT APPLY |
| | TO THIS BUILDING. |
| | |
| | 23- SHEET A706.2: PROVIDE ONLY THE DETAILS THAT APPLY |
| | TO THIS BUILDING. |
| | |
| | 24- SHEET A707: PROVIDE ONLY THE DETAILS THAT APPLY TO |
| | THIS BUILDING. |
| | |
| | 25- SHEET A810: |
| | A) SEE COMMENTS ONSHEET A004 REGARDING OCCUPANT |
| | LOAD. |
| | B) SEE PLUMBING COMMENTS REGARDING PROPER FACILITY |
| | USE.FINAL FLOOR LAYOUTMAY AFFECT CALCULATIONS ON |
| | SHEET A004 AS WELL. |
| | C) MULTIPURPOSE ROOM AND COUNSELING AREA MAY BE |
| | COMBINED ALSO. TAKE THIS IN CONSIDERATION WHEN DOING |
| | OCCUPANT LOAD CALCULATIONS. |
| | D) NUMBER OF PEOPLE MAY AFFECT NUMBER OF EGRESS |
| | DOORS REQUIRED. |
| | |
| | 26- SHEET S-2: TRUSS TIE DOWN SCHEDULE. REVISE NOTE #6 |
| | FOR CONNECTOR C (SIMPSON MGT). NEED 12" EMBEDMENT. SEE |
| | SIMPSON CATALOGUE. |
| | |
| | 27- PROVIDE COMPLETE DETAILS AND SPECS FOR INSTALLATION |
| | OF RECESSED GAS WATER HEATER. PROVIDE DETAILS AND SPECS |
| | FOR WALL SEPARATING WATER HEATER AND AIR HANDLER UNIT. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |