| Plan Review Notes For Permit 06101050 |
| Permit Number |
06101050 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-20 11:01:28 | *****DENIED***** | | | | | | | | | | | | 1.SINCE THE CONTRACT IS GREATER THAN $2500.00, THE | | | APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED | | | NOTICE OF COMMENCEMENT OR A NOTORIZED STATEMENT THAT | | | THE NOTICE HAS BEEN FILED FOR RECORDING, ALONG WITH A | | | COPY THEREOF. | | | | | | 2.SINCE THE SCOPE OF WORK IS GREATER THAN $5,000.00 | | | AS PER FLORIDA ADMINISTRATIVE CODES, A PROFESSIONAL | | | ENGINEER SHALL SIGN HIS SEAL TO ALL PLANS, | | | SPECIFICATIONS, ETC TO BE FILED FOR PUBLIC RECORD.THE | | | STAMPED ENGINEERED SEAL SHALL HAVE THE WORDING | | | "LICENSE" IN LIEU OF "CERTIFICATE". | | | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 4.CONSTRUCTION AND/OR DEMOLITIONS OPERATIONS SHALL | | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEREOF. | | | | | | 5.WILL ANY FIRE PROTECTION SYSTEMS BE AFFECTED BY THE | | | SCOPE OF THE WORK? | | | | | | 6.WILL THE BUILDING OR PORTIONS OF THE BUILDING BE | | | OCCUPIED DURING THE SCOPE OF THE WORK?IF SO, HOW WILL | | | THE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE | | | PROTECTION FEATURES BE KEPT IN PLACE AND MAINTAINED? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|