| 2007-02-11 13:34:16 | *** UNSAT 4TH REVIEW*** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW NOTES AS STATED |
| | BELOW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE IN ALL PREVIOUS REVIEWS IT WAS |
| | REQUESTED THAT ALL OLD/VOIDED SHEETS BE REMOVED FROM |
| | SETS AND TO INSERT NEW REVISED SHEETS INTO SETS, PLEASE |
| | INSERT NEW SHEETS AND ATTACH INTO SETS. PLEASE DO NOT |
| | ONLY INSERT SHEET LOOSELY INTO SETS. |
| | THIS WILL HELP IN PROCESSING THE PLANS FOR PERMITTING. |
| | |
| | 2) NOTE: PLEASE SEE THE ORIGINAL REVIEW REQUESTED |
| | ENERGY CALCULATIONS AND PERFORMANCE CALCULATIONS WHICH |
| | MET THE 2004 FBC AND CHAPTER 13. THESE WERE SUBMITTED |
| | FOR REVIEW FOR THE 2ND REVIEW AND 3RD REVIEW WHICH |
| | NOTES REQUESTED FOR COMPLIANCE AND FOR ALL CALCULATIONS |
| | TO CORRELATE WITH THE PLANS SUBMITTED AND THERE WERE |
| | SUBSTANTIAL DIFFERENCES IN THE NUMBER OF FIXTURES, |
| | LOADS, WATTAGE(S), ETC. |
| | PLEASE SEE THAT THIS COMMENT IS STILL BEING MADE AS THE |
| | ENERGY CALCULATIONS DO NOT CORRELATE WITH PLANS OR |
| | FIXTURE LEGEND FOR FIXTURES, NUMBER OF FIXTURES, |
| | WATTAGES OF FIXTURES ETC. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT MATCH. |
| | PLEASE SEE OUTSIDE/EXTERIOR FIXTURES, PLEASE SEE |
| | INTERIOR FIXTURES ETC |
| | PLEASE SEE ALL. |
| | THE TOTALS DO NOT CORRELATE, TOTALS ON SOME OF THE |
| | FIXTURES ON FIXTURE LEGEND DOES NOT MATCH WITH PLANS |
| | AND # OF FIXTURES AS SHOWN. ETC. |
| | THIS WAS STATED IN ALL REVIEWS AFTER THE 1ST REVIEW AS |
| | THESE WERE SUBMITTED ON THE FIRST REVIEW WHICH WAS |
| | STILL REQUIRED UNDER THE 2004 FBC. |
| | PLEASE SEE THAT A METHOD A IS STILL BEING SHOWN, |
| | HOWEVER IT IS NOT CLEAR HOW THIS IS BEING USED WHEN |
| | THIS IS FOR TOTAL BUILDING COMPLIANCE AND OTHER AREAS |
| | AND TRADES OFFS ARE NOT BEING SHOWN OR INDICATED. |
| | (PREVIOUS REVIEWS). |
| | PLEASE SEE THE ELECTRICAL PLANS FOR FIXTURES WERE |
| | REVISED TO DELETE MANY FIXTURES HOWEVER THE |
| | ARCHITECTURAL AND LIFE SAFETY SHEETS WERE NOT REVISED |
| | TO REFLECT THESE CHANGES. |
| | PLEASE SEE FBC 2004 13-415.1.AB.1. |
| | PLEASE SEE 13-415.2. |
| | |
| | 3) NOTE: PLEASE SEE THE WIND LOADS SEEMS TO BE OK, |
| | HOWEVER WILL BE REVIEWED BY THE STRUCTURAL REVIEWER. |
| | PLEASE SEE THE ELECTRICAL SHEETS STILL NOT INDICATE ANY |
| | REFERENCE TO THE 140MPH WIND LOAD REQUESTED ON PREVIOUS |
| | REVIEW. |
| | |
| | ** NEW NOTES DUE TO PLANS SUBMITTED AND CHANGES WHICH |
| | WERE NOT ON PREVIOUS PLANS. |
| | |
| | 3) NOTE: PLEASE SEE RISER NOW SHOWS *EQUIPMENT |
| | GROUNDING CONDUCTORS FROM THE GUTTER TO THE FIRST MEANS |
| | OF DISCONNECT IS NOT PERMITTED PER 250.6. |
| | PLEASE SEE THE PREVIOUS COMMENTS REQUESTED TO SHOW THE |
| | CONDUCTORS FROM THE GUTTER TO EACH MAIN AND FOR * |
| | EQUIPMENT GROUNDING CONDUCTORS* AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | PLEASE SEE 250.6 AND 250.24B AS THIS NOW CREATES |
| | OBJECTIONABLE CURRENTS BY PARALLELING THE NEUTRAL. |
| | PLEASE SEE THIS WOULD HAVE BEEN REDLINED, HOWEVER AS |
| | PLANS ARE COMING BACK FOR COMMENT #2, PLEASE CORRECT AT |
| | THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE AS COMMENT #2 HAS BEEN REPEATED FOR |
| | CODE COMPLIANCE REVIEW THREE OR MORE TIMES FOR THE SAME |
| | CODE COMPLIANT COMMENT AND IT IS NECESSARY FOR THIS |
| | OFFICE TO REJECT PLANS FOR THIS, THE FS 553.80(2)(B) IS |
| | IN EFFECT AND A 4X FEE FOR THE PLAN REVIEW PORTION OF |
| | THE PERMIT FEE HAS NOW BEEN ASSESSED. |
| | THIS FEE IS A REQUIRED FEE PER THE FLORIDA STATUTES TO |
| | THE DESIGNER(S) OF RECORD AND MUST BE PAID BEFORE PLANS |
| | CAN BE RESUBMITTED FOR REVIEW. |
| | PLEASE SEE THAT ONE SET OF EACH ELECTRICAL PLAN AND |
| | ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE. |
| | ONE SET OF THE ARCHITECTURAL AND LS PLANS MAY ALSO BE |
| | RETAINED. |
| | THE AMOUNT OF $1620 WILL BE DUE BEFORE PLANS CAN BE |
| | RESUBMITTED. |
| | |
| | ** IT IS RECOMMENDED THAT COMMENT #2 BE REVIEWED AND |
| | GONE THROUGH THOROUGHLY. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |