| Plan Review Notes For Permit 06101031 |
| Permit Number |
06101031 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-01-09 09:00:55 | DENIED; | | | 1. (FROM FIRST REVIEW #3NOT ADDRESSED) SHOW TOTAL | | | NUMBER OF EMPLOYEES MUST COMPLY WITH FBC-2004 TABLE | | | 403.1 (2B). SEPARATE FACILITIES EXCEPTIONS FOR SECTION | | | 403.2 MUST BE SHOWN ON PLANS. | | | 2. DEMO PLAN REQUIRED SHOWING ALL EXISTING PLUMBING TO | | | BE REMOVED. ADD NOTE TO DEMO PAGE "NO DEAD ENDS | | | PERMITED IN SANITARY DRAINAGE SYSYEM, INSPECTION | | | REQUIRED) SEE SECTION 704.5 DEAD ENDS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|