| Date |
Text |
| 2007-01-05 20:28:58 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE CORRELATE ELECTRICAL AND BUILDING |
| | PLANS. |
| | PLEASE SEE THE OFFICE SPACES IN THE ARCHITECTURAL |
| | SHEETS ARE BEING SHOWN NOT IN SCOPE OF WORK; HOWEVER |
| | THE ELECTRICAL SHEETS CLEARLY ARE INCLUDING THE |
| | ELECTRICAL AS REQUIRED IN SCOPE. |
| | PLEASE COMPLETE AND SEE THE FOLLOWING COMMENT. |
| | FBC 106.1.2 AND 106.3.5.1.2 FOR ADDITIONAL INFORMATION |
| | NEEDED. |
| | |
| | 2) NOTE: PLEASE SEE THE FBC 2004 METHOD A ENERGY |
| | CALCULATIONS DO NOT CORRELATE WITH THE SAME SQUARE |
| | FOOTAGE ON THE PLANS AND ON APPLICATION. |
| | PLEASE SEE THE ENERGY CALCULATIONS INDICATE ONLY 20, |
| | 40W LIGHT FIXTURES AND THE ELECTRICAL PLANS SHOW |
| | LIGHTING FIXTURES IN EXCESS OF WELL OVER 150+ |
| | FIXTURES. |
| | PLEASE PROVIDE COMPLETED ENERGY CALCULATIONS WHICH |
| | CORRELATE WITH THE ELECTRICAL PLANS FOR ALL LIGHTING |
| | AND ENERGY USAGE. |
| | PLEASE SEE FBC 13-415.1.AB.1 |
| | |
| | 3) NOTE: PLEASE SEE 220.12 FOR LOADS ON TRACK LIGHTING |
| | TO BE SHOWN. |
| | |
| | 4) NOTE: PLEASE SEE THE NOTE ADDED FOR WIND LOADS FOR |
| | LIGHT POLES IS NOT ENOUGH AND MAKES NO MENTION OF EVEN |
| | THE WIND LOAD RATINGS ETC. PLEASE SEE THE PREVIOUS |
| | REVIEW NOTE. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |