| 2006-11-03 18:49:48 | ** UNSAT *** |
| | |
| | 1) NOTE: PLEASE PROVIDE SIGNED, DATED AND SEALED WIND |
| | LOAD CALCULATIONS FOR THE NEW PROPOSED SITE LIGHTING |
| | POLES. PLEASE BE SURE THE CALCULATIONS INCLUDE THE EPA |
| | FOR THE LIGHTING FIXTURES WHICH WILL BE INSTALLED. |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR 140MPH 3 SECOND |
| | GUST, 120SUSTAINED. ETC |
| | |
| | 2) NOTE: PLEASE INCLUDE THE FOLLOWING RELEVANT CODES ON |
| | PLANS AND DESIGN. |
| | 2002 NFPA-70 (NEC), 2003 NFPA-101, 2002 NFPA-72 (WHEN |
| | APPLICABLE). |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL PANEL IS NOT PERMITTED |
| | IN OFFICE / STORAGE AREA. PLEASE SEE 240.24D, 408.7, |
| | 110.26 ETC. |
| | PLEASE RELOCATE. |
| | |
| | 4) NOTE: PLEASE SEE 250.6 AND 250.24 AS AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" IS BEING INDICATED AHEADOF THE |
| | MAIN DISCONNECT. |
| | PLEASE KNOW, THIS SHALL ONLY BE INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 5) NOTE: PLEASE CORRELATE THE EQUIPMENT GROUNDING |
| | CONDUCTOR ON RISER WITH THAT LISTED ON PANEL SCHEDULE. |
| | PLEASE SEE 250.122, |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE MISSING CWP AS PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. 250.50 |
| | |
| | 7) NOTE;: PLEASE SEE LOBBY WILL REQUIRED AN EMERGENCY |
| | BATTERY BACK UP LT OF SOME SORT TO MEET THE MIN |
| | LIGHTING LEVELS REQUIRED PER LS 101 7.8, 7.9 . (COMBO |
| | UNITS, MAY BE USED). (ONLY A SUGGESTION. |
| | |
| | 8) NOTE: PLEASE PROVIDE CLARIFICATION OF ADJACENT |
| | OFFICE SPACE , NOTED A CONSTRUCTION OFFICES. IS THIS |
| | STILLPART OF THE SAME TENANT? |
| | |
| | 9) NOTE: PLEASE CLARIFY THE ADJUSTEDSQ FT FOR SPACE. |
| | PLEASE SEE PERMIT APPLICATION, ENERGY CALCULATIONS, AND |
| | PLANS. |
| | PLEASE KNOW IF BLDG IS OVER 5K SQ FT, FBC 2004 CHAPTER |
| | WILL APPLY. |
| | PLEASE SEE 13-415.1.AB.1 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |