| Plan Review Notes For Permit 06101026 |
| Permit Number |
06101026 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-12 15:00:15 | | | | DENIED BY BUILDING | | | | | | 1) THE LIVE LOAD SPECIFIED FOR THE DECK IS TOO LOW. | | | 2004 FBC TABLE 1607.1 REQUIRES DECKS TO HAVE A LIVE | | | LOAD THE SAME AS THE OCCUPANCY IT SERVES. THIS DECK | | | SERVES A CLUB HOUSE, WHICH IS AN ASSEMBLY OCCUPANCY | | | WITH 100 PSF LIVE LOAD. | | | | | | 2) SPECIFY THE CENTER TO CENTER SPACING OF THE 2 X 12 | | | FLOOR JOISTS ON THE PLANS. | | | | | | 3) THE EXISTING FENCE IS REQUIRED TO COMPLY WITH 2004 | | | FBC 424.1.3.1.9 FOR POOL BARRIERS. | | | | | | 4) SPECIFY THE DISTANCE FROM THE POOL TO THE WOOD DECK. | | | SEE FBC 424.1.3.1.1 FOR POOL WET DECK REQUIREMENTS. | | | | | | 5) POOL FENCE IS REQUIRED TO COMPLY WITH FBC 1012 FOR | | | GUARDS. | | | | | | 6) PLANS DO NOT SPECIFY THE SPECIES OFWOOD THAT WILL | | | BE USED FOR THE DECK OR IF IT IS PRESERVATIVE TREATED. | | | PLEASE CLARIFY. | | | | | | 7)A RESIDENTIAL CONTRACTOR IS LIMITED TO WORK ON | | | ONE-, TWO- AND THREE-FAMILY RESIDENCES AND ACCESSORY | | | USE STRUCTURES IN CONNECTION THEREWITH. THIS DECK IS | | | ACCESSORY TO A CLUB HOUSE WHICH IS A COMMERCIAL | | | BUILDING. THIS PROJECT CAN NOT BE DONE BY A RESIDENTIAL | | | CONTRACTOR. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|