 ** REVISION DENIED **
  
  
 1) NOTE: PLEASE SEE HOLD WHICH WAS PLACED ON PROJECT BY
 THE INSPECTION SERVICES MANAGER FOR LEVEL OF ALTERATION
 AND PERMITS WHICH HAVE NOT BEEN APPLIED FOR.
  
 2) NOTE: PLEASE SEE THERE WERE ITEMS REDLINED ON
 PREVIOUS PLANS WHICH HAVE NOT BEEN ADDED TO PLANS.
 A) PLEASE SEE MISSING CODE REFERENCES:
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 FBC 2004.
  
 B) PLEASE SEE MISSING CIRCUITS TO BE INDICATED ON PANEL
 SCHEDULE FOR ARC FAULT PROTECTION.210.12,408.4
  
 C) PLEASE SEE MISSING RECEPTACLES IN KITCHEN WITH
 GREATER THAN 2FT OF WALL SPACE. THIS WAS ADDED TO TWO
 UNITS AS THIS WAS A NOTE IN THE REVIEW DATED
 02/15/07.
 210.52
  
 3) NOTE: PLEASE CLEARLY INDICATE THE REVISIONS ON PLANS
 WITH CLOUDS/TRIANGLES ETC.
 PLEASE REVISE PLANS AND TITLE BLOCKS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE AREA ANY
 QUESTIONS, PLEASE CALL.
  