| Plan Review Notes For Permit 06101014 |
| Permit Number |
06101014 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-12 10:56:34 | | | | | | | ** REVISION DENIED ** | | | | | | | | | 1) NOTE: PLEASE SEE HOLD WHICH WAS PLACED ON PROJECT BY | | | THE INSPECTION SERVICES MANAGER FOR LEVEL OF ALTERATION | | | AND PERMITS WHICH HAVE NOT BEEN APPLIED FOR. | | | | | | 2) NOTE: PLEASE SEE THERE WERE ITEMS REDLINED ON | | | PREVIOUS PLANS WHICH HAVE NOT BEEN ADDED TO PLANS. | | | A) PLEASE SEE MISSING CODE REFERENCES: | | | 2002 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 | | | FBC 2004. | | | | | | B) PLEASE SEE MISSING CIRCUITS TO BE INDICATED ON PANEL | | | SCHEDULE FOR ARC FAULT PROTECTION.210.12,408.4 | | | | | | C) PLEASE SEE MISSING RECEPTACLES IN KITCHEN WITH | | | GREATER THAN 2FT OF WALL SPACE. THIS WAS ADDED TO TWO | | | UNITS AS THIS WAS A NOTE IN THE REVIEW DATED | | | 02/15/07. | | | 210.52 | | | | | | 3) NOTE: PLEASE CLEARLY INDICATE THE REVISIONS ON PLANS | | | WITH CLOUDS/TRIANGLES ETC. | | | PLEASE REVISE PLANS AND TITLE BLOCKS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION. IF THERE AREA ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 |
|