| 2007-02-15 07:24:49 | |
| | |
| | |
| | **** UNSAT **** |
| | |
| | 1) NOTE:PLEASE SEE THE CIRCUITING FOR THE SMOKE |
| | ALARMS IS SHOWING ALL THE DEVICES ON SEPARATE CIRCUITS. |
| | PLEASE SEE SOME APT UNITS ARE SHOWING AS MANY AS FOUR |
| | CIRCUITS FOR THE SMOKE ALARMS. PLEASE KNOW THAT THESE |
| | DEVICES ARE REQUIRED TO BE WIRED *INLINE* THEREFORE |
| | PLACING 220V ON THESE DEVICES AS THEY ARE ON SEVERAL |
| | CIRCUITS FOR ONE UNIT. |
| | PLEASE ADJUST ALL CIRCUITING FOR THESE AS THEY SHOULD |
| | BE ON ONE CIRCUIT. |
| | NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 2) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SHOWN FOR |
| | THE UNIT PANELS ARE NOT RESIDENTIAL LOAD CALCULATIONS. |
| | PLEASE SEE THE SECTIONS ALSO REFLECTED ON THE PANELS |
| | ARE FOR OTHER THAN DWELLING UNITS. |
| | PLEASE SEE NEC 220 PART II OR PART III. |
| | |
| | 3) NOTE: PLEASE SEE THE PREVIOUS NOTES MENTIONED THE |
| | MISSING WASHER/LAUNDRY CIRCUIT. PLEASE SEE THIS IS NOW |
| | SHOWN ON PANEL SCHEDULE; HOWEVER THE MINIMUM LOAD ON |
| | THIS CIRCUIT IS REQUIRED TO BE 1500VA PER 220.16B. |
| | PLEASE ALSO SEE THAT THE LOAD CALCULATIONS DO NOT |
| | INDICATE OR SHOW THE WASHER/LAUNDRY LOAD BEING |
| | FIGURED. |
| | 210.11C2 |
| | |
| | 4) NOTE: PLEASE SEE A COUPLE OF MISSING RECEPTACLES PER |
| | 210.52 FOR WALL SPACE TWO FEET OR MORE. PLEASE SEE |
| | KITCHEN WALLS IN UNITS *C* AND *D*. THERE ARE REDLINED |
| | ON ONE SET OF THE PLANS SUBMITTED. |
| | PLEASE ALSO SEE UNIT *B* WHICH DOE SHOW A RECEPTACLE ON |
| | THIS TWO FT OF WALL; HOWEVER IT IS BEING SHOWN AS A |
| | DEDICATED CIRCUIT FOR THE WALL AC UNIT. PLEASE KNOW AN |
| | ADDITIONAL RECEPT WILL BE REQUIRED. |
| | PLEASE ALSO SEE THAT THESE RECEPTACLES WHICH ARE |
| | MISSING ARE REQUIRED TO BE ON ONE OR MORE OF THE SMALL |
| | APPLIANCE CIRCUITS. (210.52B1) |
| | |
| | 5) NOTE: PLEASE SEE 110.26 FOR THE MINIMUM REQUIRED |
| | CLEARANCES FOR THE CU DISCONNECTS. |
| | PLEASE SEE THAT THESE ARE BEING SHOWN WITH LESS THAN |
| | THE 30 INCHES MINIMUM SIDE TO SIDE REQUIRED. PLEASE SEE |
| | SOME WITH LESS THAN 1FT BASED ON THE 3/8 INCHES SCALE |
| | AS NOTED ON PLANS. |
| | PLEASE ADJUST LAYOUT OF ALL EQUIPMENT AS SHOWN DOWN THE |
| | SIDE FOR THESE UNITS. |
| | |
| | 6) NOTE: PLEASE LIST AND INDICATE THE ARC FAULT |
| | PROTECTED BREAKERS ON PANEL SCHEDULE. A NOTE WAS |
| | LOCATED ON THE APARTMENT LAYOUT PLANS; HOWEVER PLEASE |
| | LIST THE BREAKERS ON PANEL SCHEDULE. |
| | 210.12 |
| | FBC 106.1.2, 106.3.5.4 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE SEE THE RISER DIAGRAM INDICATES |
| | GROUNDING ELECTRODE PER NEC WHOEVER PLEASE INDICATE THE |
| | MINIMUM REQUIRED.PLEASE SHOW A MINIMUM OF TOW GROUND |
| | RODS AND COLD WATER PIPE (IF METAL). |
| | 250.50, 250.56 |
| | CODE MAY NOT BE QUOTED IN LIEU OF SPECIFIC OR TECHNICAL |
| | DETAIL. |
| | |
| | 8) NOTE: PLEASE SHOW THE LOCATION AND THE SERVICE ON |
| | PLANS. (METERS AND RISER)VERIFICATION FOR 110.26 ETC |
| | NEEDS TO BE VERIFIED. ALSO OVER HEAD CLEARANCES FROM |
| | 2ND FLOOR WINDOWS SHOULD BE TAKEN INTO CONSIDERATION |
| | BASED ON SERVICE RISER LOCATION. (3FT MINIMUM |
| | REQUIRED). |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |