Plan Review Notes
Plan Review Notes For Permit 06101014
Permit Number 06101014
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-15 07:24:49 
  
  
 **** UNSAT ****
  
 1) NOTE:PLEASE SEE THE CIRCUITING FOR THE SMOKE
 ALARMS IS SHOWING ALL THE DEVICES ON SEPARATE CIRCUITS.
 PLEASE SEE SOME APT UNITS ARE SHOWING AS MANY AS FOUR
 CIRCUITS FOR THE SMOKE ALARMS. PLEASE KNOW THAT THESE
 DEVICES ARE REQUIRED TO BE WIRED *INLINE* THEREFORE
 PLACING 220V ON THESE DEVICES AS THEY ARE ON SEVERAL
 CIRCUITS FOR ONE UNIT.
 PLEASE ADJUST ALL CIRCUITING FOR THESE AS THEY SHOULD
 BE ON ONE CIRCUIT.
 NFPA-72 11.5.1.1, 11.8.3
  
 2) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SHOWN FOR
 THE UNIT PANELS ARE NOT RESIDENTIAL LOAD CALCULATIONS.
 PLEASE SEE THE SECTIONS ALSO REFLECTED ON THE PANELS
 ARE FOR OTHER THAN DWELLING UNITS.
 PLEASE SEE NEC 220 PART II OR PART III.
  
 3) NOTE: PLEASE SEE THE PREVIOUS NOTES MENTIONED THE
 MISSING WASHER/LAUNDRY CIRCUIT. PLEASE SEE THIS IS NOW
 SHOWN ON PANEL SCHEDULE; HOWEVER THE MINIMUM LOAD ON
 THIS CIRCUIT IS REQUIRED TO BE 1500VA PER 220.16B.
 PLEASE ALSO SEE THAT THE LOAD CALCULATIONS DO NOT
 INDICATE OR SHOW THE WASHER/LAUNDRY LOAD BEING
 FIGURED.
 210.11C2
  
 4) NOTE: PLEASE SEE A COUPLE OF MISSING RECEPTACLES PER
 210.52 FOR WALL SPACE TWO FEET OR MORE. PLEASE SEE
 KITCHEN WALLS IN UNITS *C* AND *D*. THERE ARE REDLINED
 ON ONE SET OF THE PLANS SUBMITTED.
 PLEASE ALSO SEE UNIT *B* WHICH DOE SHOW A RECEPTACLE ON
 THIS TWO FT OF WALL; HOWEVER IT IS BEING SHOWN AS A
 DEDICATED CIRCUIT FOR THE WALL AC UNIT. PLEASE KNOW AN
 ADDITIONAL RECEPT WILL BE REQUIRED.
 PLEASE ALSO SEE THAT THESE RECEPTACLES WHICH ARE
 MISSING ARE REQUIRED TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS. (210.52B1)
  
 5) NOTE: PLEASE SEE 110.26 FOR THE MINIMUM REQUIRED
 CLEARANCES FOR THE CU DISCONNECTS.
 PLEASE SEE THAT THESE ARE BEING SHOWN WITH LESS THAN
 THE 30 INCHES MINIMUM SIDE TO SIDE REQUIRED. PLEASE SEE
 SOME WITH LESS THAN 1FT BASED ON THE 3/8 INCHES SCALE
 AS NOTED ON PLANS.
 PLEASE ADJUST LAYOUT OF ALL EQUIPMENT AS SHOWN DOWN THE
 SIDE FOR THESE UNITS.
  
 6) NOTE: PLEASE LIST AND INDICATE THE ARC FAULT
 PROTECTED BREAKERS ON PANEL SCHEDULE. A NOTE WAS
 LOCATED ON THE APARTMENT LAYOUT PLANS; HOWEVER PLEASE
 LIST THE BREAKERS ON PANEL SCHEDULE.
 210.12
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE THE RISER DIAGRAM INDICATES
 GROUNDING ELECTRODE PER NEC WHOEVER PLEASE INDICATE THE
 MINIMUM REQUIRED.PLEASE SHOW A MINIMUM OF TOW GROUND
 RODS AND COLD WATER PIPE (IF METAL).
 250.50, 250.56
 CODE MAY NOT BE QUOTED IN LIEU OF SPECIFIC OR TECHNICAL
 DETAIL.
  
 8) NOTE: PLEASE SHOW THE LOCATION AND THE SERVICE ON
 PLANS. (METERS AND RISER)VERIFICATION FOR 110.26 ETC
 NEEDS TO BE VERIFIED. ALSO OVER HEAD CLEARANCES FROM
 2ND FLOOR WINDOWS SHOULD BE TAKEN INTO CONSIDERATION
 BASED ON SERVICE RISER LOCATION. (3FT MINIMUM
 REQUIRED).
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]