Plan Review Notes
Plan Review Notes For Permit 06101014
Permit Number 06101014
Review Stop P
Sequence Number 1
Notes
Date Text
2006-11-17 12:37:53DENIED;
 1. PLEASE ADD NOTE TO PLUMBING PAGE. "A REDUCED
 PRESSURE PRINCIPAL BACKFLOW PREVENTOR TO BE INSTALLED
 ON THE BUILDING SIDE OF THE
 WATER METER"
 2. PLEASE SHOW BATHROOM MEASUREMENTS IN BATHROOMS WHERE
 THE LAVATORYS WERE MOVED. A DISTANCE OF 30" IS REQUIRED
 FROM THE CENTERLINE
 OF TOILET TO THE CENTERLINE OF THE LAVATORY, AND
 15" TO THE EDGE OF THE TUB TO THE CENTERLINE OF THE
 TOILET. FBC-2004 PLUMBING SECTION
 405.3.1
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695