| 2006-11-21 12:08:36 | *****DENIED***** |
| | |
| | |
| | |
| | 01.PLEASE PROVIDE A LAYOUT OF THE STRUCTURE ON A SITE |
| | PLAN AS TO HOW IT RELATES TO THE NEAREST STREETS, |
| | HYDRANTS, RAILROAD, ETC. |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE |
| | SAID PROPERTY OR VICINITY THEREOF. |
| | |
| | 04.FIRE EXTINGUISHERS TO BE RATED 2A-10 BC. |
| | |
| | 05.PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE |
| | TIED INTO A FIRE ALARM SYSTEM.THE DEVICES USED AT THE |
| | SITE ARE SMOKE ALARMS (SA) AND SHOULD BE REFLECTED AS |
| | SUCH IN THE SUBMITTED PLANS. |
| | |
| | 06.FOR SPECIFIC LOCATION REQUIREMENTS OF SMOKE |
| | ALARMS/SMOKE DETECTORS, NFPA 72 - 2002 EDITION - |
| | 11.8.3.5 SHALL BE REFERENCED. |
| | |
| | 07.SMOKE ALARMS INSTALLED WITHIN 20-FT HORIZONTAL |
| | PATH OF A COOKING APPLIANCE SHALL BE EQUIPPED WITH AN |
| | ALARM SILENCING MEANS OR BE OF THE PHOTOELECTRIC TYPE. |
| | |
| | 08.SMOKE ALARMS SHALL RECEIVE ITS OPERATING POWER |
| | FROM THE BUILDING'S ELECTRICAL SERVICE. |
| | |
| | 09.INSTALL A SMOKE ALARM IN THE LIVING AREA OF THE |
| | UNITS. |
| | |
| | 10. INTERIOR FINISH FOR WALLS AND CEILING SHALL BE |
| | CLASS "A" OR CLASS "C".PLEASE SPECIFY. |
| | |
| | 11. VERITY THAT THE NUMERICAL ADDRESS (ON THE BUILDING) |
| | IS NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH PLAINLY |
| | VISIBLE FROM 16TH STREET.EACH UNIT SHALL HAVE A |
| | NUMBER OR ALPHABET NO LESS THAN 3" IN HEIGHT ABOVE OR |
| | IN THE VICINITY OF THE FRONT DOOR (NOT ON THE DOOR). |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |