Plan Review Notes
Plan Review Notes For Permit 06101014
Permit Number 06101014
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-01 09:40:43*******UNSAT *********
  
  
 ** PLEASE SEE THIS IS A NEW REVIEW UNDER A NEW PERMIT,
 HOWEVER THIS WAS REVIEWEDUNDER 05111120. PLEASE SEE
 SOME COMMENTS FROM THE FIRST TWO REVIEWS STILL ARE
 NOTED.
  
 1) NOTE:PLEASE BE SURE THE RELEVANT CODES ARE
 REQUIRED TO BE STATED ON PLANS AS FOLLOWS:
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101.
 PLEASE ALSO SEE COMMENT WITH RESPECT THE FHA.
  
 2) NOTE: PLEASE SHOW AND COMPLETE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE "SD", HOWEVER SEE OTHER NOTE FOR THESE.
 PLEASE ALSO SEE NOTE ABOUT WASHER ETC.
 FBC 106.1.2 ADMIN SECT.
  
 3) NOTE: PLEASE SEE NFPA DEFINITIONS FOR SMOKE
 DETECTORS AND SMOKE ALARMS. PLEASE KNOW IF THESE ARE
 INDEED DEVICES WHICH DETECT AND CONTAIN THE AUDIBLE
 ALARM, THESE SHOULD BE NOTED AS SA. PLEASE KNOW A SD
 DEVICE IS A DETECTION DEVICE ONLY AND WOULD SIGNAL AND
 ALARM PANEL OR HORNS OF SOME TYPE.
 PLEASE KNOW THIS WAS RECENTLY GONE OVER WITH NFPA AND
 THE CODE COUNSEL.
  
 4) NOTE: PLEASE INDICATE ALL CONDUCTORS FROM METER BANK
 TO THE MAIN DISCONNECTS.
 310.16, 240.4
  
 5) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR"
 IS BEING SHOWN IN THE RISER BEFORE THE FIRST MEANS OF
 DISCONNECT?
 PLEASE SEE 250.6, AND 250.24B.
  
 6) NOTE: PLEASE SEE RISER SEEMS TO INDICATE BUILDING
 STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM,
 HOWEVER PLEASE VERIFY THIS AS THIS IS AN EXISTING
 BUILDING AND IF SHOWN, THEN THIS WOULD BE REQUIRED.
 250.50.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 210.52 FOR SOME MISSING RECEPTS
 FOR 2FT OR MORE OF WALL , WITHIN 6FT OF DOOR, AND 12 FT
 OR MORE OF WALL SPACE.
  
 8) NOTE: PLEASE SEE FHAR 24 CFR 100.205 FOR FIRST FLOOR
 DEVICES TO BE SHOWN AND NOTED.
  
 9) NOTE: PLEASE SEE UNIT "A" WHICH SHOWS A KITCHEN GFI
 RECEPT ON THE KITCHEN LIGHTING CIRCUIT WHICH IS NOT
 PERMITTED. PLEASE SEE 210.52B1.
  
 10) NOTE: PLEASE SEE NO CIRCUIT OR RECEPT DEVICE SHOWN
 FOR UNIT "A" WASHER.
 210.11C2,
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE 210.52B1, WHICH REQUIRES RECEPTS
 LOCATED ON DINING/KITCHEN/ BREAKFAST AREAS AND THE LIKE
 SHALL BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE SOME AREAS WHICH FIT INTO THIS
 DESCRIPTION OR DESIGNATION HOWEVER THEY ARE ON GENERAL
 LIGHTING CIRCUITS WHICH IS NOT PERMITTED.
  
 12) NOTE: PLEASE PROVIDE THE MIN LIGHTING LEVELS FOR
 STAIRS UNDER NORMAL POWER FOR MIN EGRESS REQUIREMENTS
 PER NFPA-101 7.8.1.3, AND MIN LEVELS UNDER
 EMERGENCY.7.9.2.2
 A BATTERY BACK UP FIXTURE OF SOME SORT WILL BE REQUIRED
 FOR EMERGENCY EGRESS TO THE PUBLIC RIGHT OF WAY.
 PLEASE ALSO CLARIFY HOW THIS LIGHTING FROM THE HOUSE
 PANEL IS BEING CONTROLLED??
  
 13) NOTE: PLEASE SUBMIT SPEC FOR OUTSIDE WATER HEATER
 UNITS FROM THE MANUFACTURE INDICATING LISTINGS FROM
 NRTL.
 110.3, 90.7
 FBC 106.1.2
  
 14) NOTE: PLEASE CORRELATE MECHANICAL PLANS WITH
 ELECTRICAL FOR SIZING OF THE HEAT IN THE AHU'S. PLEASE
 SEE THESE ARE BEING SHOWN AS 10KW, HOWEVER PLEASE SEE
 MECH PLANS INDICATE 5KW?
 FBC 106.1.2, NEC 424.3B, 310.16
 ** PLEASE SEE A NAX OCP DEVICE IS ALSO USUALLY SET BY
 THE MANUFACTURE HOWEVER TYPICALLY 150%.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  