| Date |
Text |
| 2006-11-01 09:40:43 | *******UNSAT ********* |
| | |
| | |
| | ** PLEASE SEE THIS IS A NEW REVIEW UNDER A NEW PERMIT, |
| | HOWEVER THIS WAS REVIEWEDUNDER 05111120. PLEASE SEE |
| | SOME COMMENTS FROM THE FIRST TWO REVIEWS STILL ARE |
| | NOTED. |
| | |
| | 1) NOTE:PLEASE BE SURE THE RELEVANT CODES ARE |
| | REQUIRED TO BE STATED ON PLANS AS FOLLOWS: |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101. |
| | PLEASE ALSO SEE COMMENT WITH RESPECT THE FHA. |
| | |
| | 2) NOTE: PLEASE SHOW AND COMPLETE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULES. |
| | PLEASE SEE "SD", HOWEVER SEE OTHER NOTE FOR THESE. |
| | PLEASE ALSO SEE NOTE ABOUT WASHER ETC. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 3) NOTE: PLEASE SEE NFPA DEFINITIONS FOR SMOKE |
| | DETECTORS AND SMOKE ALARMS. PLEASE KNOW IF THESE ARE |
| | INDEED DEVICES WHICH DETECT AND CONTAIN THE AUDIBLE |
| | ALARM, THESE SHOULD BE NOTED AS SA. PLEASE KNOW A SD |
| | DEVICE IS A DETECTION DEVICE ONLY AND WOULD SIGNAL AND |
| | ALARM PANEL OR HORNS OF SOME TYPE. |
| | PLEASE KNOW THIS WAS RECENTLY GONE OVER WITH NFPA AND |
| | THE CODE COUNSEL. |
| | |
| | 4) NOTE: PLEASE INDICATE ALL CONDUCTORS FROM METER BANK |
| | TO THE MAIN DISCONNECTS. |
| | 310.16, 240.4 |
| | |
| | 5) NOTE: PLEASE SEE AN "EQUIPMENT GROUNDING CONDUCTOR" |
| | IS BEING SHOWN IN THE RISER BEFORE THE FIRST MEANS OF |
| | DISCONNECT? |
| | PLEASE SEE 250.6, AND 250.24B. |
| | |
| | 6) NOTE: PLEASE SEE RISER SEEMS TO INDICATE BUILDING |
| | STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM, |
| | HOWEVER PLEASE VERIFY THIS AS THIS IS AN EXISTING |
| | BUILDING AND IF SHOWN, THEN THIS WOULD BE REQUIRED. |
| | 250.50. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE 210.52 FOR SOME MISSING RECEPTS |
| | FOR 2FT OR MORE OF WALL , WITHIN 6FT OF DOOR, AND 12 FT |
| | OR MORE OF WALL SPACE. |
| | |
| | 8) NOTE: PLEASE SEE FHAR 24 CFR 100.205 FOR FIRST FLOOR |
| | DEVICES TO BE SHOWN AND NOTED. |
| | |
| | 9) NOTE: PLEASE SEE UNIT "A" WHICH SHOWS A KITCHEN GFI |
| | RECEPT ON THE KITCHEN LIGHTING CIRCUIT WHICH IS NOT |
| | PERMITTED. PLEASE SEE 210.52B1. |
| | |
| | 10) NOTE: PLEASE SEE NO CIRCUIT OR RECEPT DEVICE SHOWN |
| | FOR UNIT "A" WASHER. |
| | 210.11C2, |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE 210.52B1, WHICH REQUIRES RECEPTS |
| | LOCATED ON DINING/KITCHEN/ BREAKFAST AREAS AND THE LIKE |
| | SHALL BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRCUITS. PLEASE SEE SOME AREAS WHICH FIT INTO THIS |
| | DESCRIPTION OR DESIGNATION HOWEVER THEY ARE ON GENERAL |
| | LIGHTING CIRCUITS WHICH IS NOT PERMITTED. |
| | |
| | 12) NOTE: PLEASE PROVIDE THE MIN LIGHTING LEVELS FOR |
| | STAIRS UNDER NORMAL POWER FOR MIN EGRESS REQUIREMENTS |
| | PER NFPA-101 7.8.1.3, AND MIN LEVELS UNDER |
| | EMERGENCY.7.9.2.2 |
| | A BATTERY BACK UP FIXTURE OF SOME SORT WILL BE REQUIRED |
| | FOR EMERGENCY EGRESS TO THE PUBLIC RIGHT OF WAY. |
| | PLEASE ALSO CLARIFY HOW THIS LIGHTING FROM THE HOUSE |
| | PANEL IS BEING CONTROLLED?? |
| | |
| | 13) NOTE: PLEASE SUBMIT SPEC FOR OUTSIDE WATER HEATER |
| | UNITS FROM THE MANUFACTURE INDICATING LISTINGS FROM |
| | NRTL. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 14) NOTE: PLEASE CORRELATE MECHANICAL PLANS WITH |
| | ELECTRICAL FOR SIZING OF THE HEAT IN THE AHU'S. PLEASE |
| | SEE THESE ARE BEING SHOWN AS 10KW, HOWEVER PLEASE SEE |
| | MECH PLANS INDICATE 5KW? |
| | FBC 106.1.2, NEC 424.3B, 310.16 |
| | ** PLEASE SEE A NAX OCP DEVICE IS ALSO USUALLY SET BY |
| | THE MANUFACTURE HOWEVER TYPICALLY 150%. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT THE ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |