| 2006-11-21 10:00:15 | *** DENIED *** |
| | 1) MANUAL J CALCULATIONS ARE FOR THE TOTAL HOUSE 1802 |
| | SQUARE FEET, THE A/C SYSTEM IS ONLY SERVING THE |
| | ADDITION 777 SQUARE FEET, PLEASE RE-DO MANUAL J |
| | CALCULATION,CORRECT ENERGY CALCULATIONS, AND |
| | EQUIPMENT LISTING ON MECHANICAL PLANS AS A RESULT. |
| | |
| | 2) SHOW SIZE OF RETURN AIR GRILL AT AHU. |
| | |
| | 3) SEE NOTES ON MECHANICAL PLAN REFER TO THE CITY OF |
| | BOYTON BEACH, PLEASE CORRECT TO CITY OF WPB. |
| | |
| | 4) RETURN AIR TRANSFER DUCT TO MASTER BEDROOM SUITE |
| | NEEDS TO BE 14", SEE NOTE #5 (A) AND (C) EXCEPT. |
| | |
| | 5) BALANCED RETURN AIR. |
| | MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |