| 2007-01-05 18:56:01 | BUILDING PLAN REVIEW |
| | PERMIT:06101011 |
| | ADD: 3202 AUSTRALIAN CT. |
| | CONT: OWNER |
| | TEL: (561)863-5754 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST. |
| | ACTION: DENIED |
| | |
| | 1)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL.MANY OF THE PRODUCT APPROVAL |
| | SUBMITTED ARE FROM THE 2001 CODE REFERENCE. THESE |
| | PRODUCTS NEED TO REFERENCE THE 2004 CODE AND THE |
| | APPLICATION STATUS HAS TO BE APPROVED. CHECK THE |
| | PROCUCT APPROVALS CARREFULLY BECAUSE THERE ARE A FEW |
| | WHICH ARE STILL PENDING FBC APPROVAL. THE PROCUCT |
| | APPROVALS SHALL BE APPROVED IN "WRITING" NOT BY |
| | STAMPING. SUBMIT UPDATED AND APPROVED PRODUCT APPROVALS |
| | WHICH SHALL BE APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD. |
| | |
| | 3)THE CLAIMED VALUATION IS TO LOW. FOR PERMITTING |
| | PURPOSES,VALUATION SHALL BE THE TOTAL REPLACEMENT VALUE |
| | TO INCLUDE STRUCTURAL,ELECTRIC, PLUMBING, |
| | MECHANICAL,INTERIOR FINISH,ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COSTS, EXCLUDING LAND VALUE.OUR |
| | VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND |
| | MEANS COST ANALYSIS SERVICES PER 103.8 FBC* |
| | |
| | 4) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF BEDROOMS |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | ) OCCUPANT LOAD |
| | ) FLOOD ZONE |
| | ) FLOOD ELEVATION |
| | )L.O.M.R. |
| | |
| | 5)R302.2 OPENINGS. |
| | OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF |
| | A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM |
| | AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET |
| | (1828 MM). THIS DISTANCE SHALL BE MEASURED |
| | PERPENDICULAR TO THE LINE USED TO DETERMINE THE |
| | SEPARATION DISTANCE. SHOW THE DISTANCE FROM THE |
| | PROPERTY LINE FOR THE NEW ADDITION WHICH WILL HAVE NEW |
| | OPENINGS. SUBMIT THIS INFORMATION ON A SITE PLAN. |
| | |
| | 6)R802.1.6.1 TRUSS DESIGN DRAWINGS. |
| | TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE WITH |
| | SECTION R802.10.1 , SHALL BE PROVIDED TO THE BUILDING |
| | OFFICIAL AND APPROVED PRIOR TO INSTALLATION. TRUSS |
| | DESIGN DRAWINGS SHALL INCLUDE, AT A MINIMUM, THE |
| | INFORMATION SPECIFIED BELOW. TRUSS DESIGN DRAWING SHALL |
| | BE PROVIDED WITH THE SHIPMENT OF TRUSSES DELIVERED TO |
| | THE JOBSITE. |
| | |
| | 7)R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| | OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 |
| | MM). |
| | |
| | 8)WHAT IS THE THICKNESS OF THE ROOF SHEATING? |
| | INDICATE ON THE DRAWINGSTHE NUMBER OF SCREEN VENT TO BE |
| | INSTALLED AND WILL MEET THE REQUIREMENTS OF SECTION |
| | R806.2. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |