Plan Review Notes
Plan Review Notes For Permit 06101011
Permit Number 06101011
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-05 18:56:01BUILDING PLAN REVIEW
 PERMIT:06101011
 ADD: 3202 AUSTRALIAN CT.
 CONT: OWNER
 TEL: (561)863-5754
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.MANY OF THE PRODUCT APPROVAL
 SUBMITTED ARE FROM THE 2001 CODE REFERENCE. THESE
 PRODUCTS NEED TO REFERENCE THE 2004 CODE AND THE
 APPLICATION STATUS HAS TO BE APPROVED. CHECK THE
 PROCUCT APPROVALS CARREFULLY BECAUSE THERE ARE A FEW
 WHICH ARE STILL PENDING FBC APPROVAL. THE PROCUCT
 APPROVALS SHALL BE APPROVED IN "WRITING" NOT BY
 STAMPING. SUBMIT UPDATED AND APPROVED PRODUCT APPROVALS
 WHICH SHALL BE APPROVED IN WRITING BY THE DESIGNER OF
 RECORD.
  
 3)THE CLAIMED VALUATION IS TO LOW. FOR PERMITTING
 PURPOSES,VALUATION SHALL BE THE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL,ELECTRIC, PLUMBING,
 MECHANICAL,INTERIOR FINISH,ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, EXCLUDING LAND VALUE.OUR
 VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES PER 103.8 FBC*
  
 4) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 ) NUMBER OF FLOORS
 ) NUMBER OF BEDROOMS
 ) NUMBER OF ROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 5)R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE. SHOW THE DISTANCE FROM THE
 PROPERTY LINE FOR THE NEW ADDITION WHICH WILL HAVE NEW
 OPENINGS. SUBMIT THIS INFORMATION ON A SITE PLAN.
  
 6)R802.1.6.1 TRUSS DESIGN DRAWINGS.
 TRUSS DESIGN DRAWINGS, PREPARED IN CONFORMANCE WITH
 SECTION R802.10.1 , SHALL BE PROVIDED TO THE BUILDING
 OFFICIAL AND APPROVED PRIOR TO INSTALLATION. TRUSS
 DESIGN DRAWINGS SHALL INCLUDE, AT A MINIMUM, THE
 INFORMATION SPECIFIED BELOW. TRUSS DESIGN DRAWING SHALL
 BE PROVIDED WITH THE SHIPMENT OF TRUSSES DELIVERED TO
 THE JOBSITE.
  
 7)R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
  
 8)WHAT IS THE THICKNESS OF THE ROOF SHEATING?
 INDICATE ON THE DRAWINGSTHE NUMBER OF SCREEN VENT TO BE
 INSTALLED AND WILL MEET THE REQUIREMENTS OF SECTION
 R806.2.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  