| Plan Review Notes For Permit 06101010 |
| Permit Number |
06101010 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-06-19 16:06:58 | THE COMMENTS FROM PREVIOUS REVIEW WERE NOT CORRECTED/ | | | PROJECT WAS PLACED ON HOLD ON 3/6/07 AS THE ENGINEER OF | | | RECORD DID NOT AGREE WITH THE ELECTRICAL PLAN REVIEW | | | COMMENTS. THIS OFFICE WAS GOING TO LET NEW | | | PLANS/DOCUMENTS TO BE BROUGHT HOWEVERNO CONTACT WAS | | | MADE. | | | FRONT COUNTER SPOKE TO LYNN ON 4/12/07TO HAVE PLANS | | | PICKED UP. PLANS ARE TO BE PICKED UP FOR CODE | | | CORRECTIONS FOR PREVIOUS COMMENTS FOR COMPLIANCE WITH | | | NEC 645 AND NFPA-75. | | | RULING UNDER THE BUILDING OFFICIAL WAS GIVEN TO THE | | | ENGINEER WITHIN A WEEK AFTER3/6/07 . SUPPORTING | | | DOCUMENTS FROM THE NEC HANDBOOK WAS FAXED TO THE | | | ENGINNEER. NO CONTACT WAS MADE AFTER THAT. | | | PLANS WERE OUT FRONT ON HOLD, HOWEVER ARE NOT PICKED UP | | | FOR CORRECTIONS. |
|