| 2006-11-04 17:34:50 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE PROVIDE AND SHOW NEW OR EXISTING |
| | ELECTRICAL DISCONNECTING MEANS FOR ALL ELECTRICAL IN |
| | THE "IT" ROOM. PLEASE SHOW THE NEW OR EXISTING "EPO" . |
| | PLEASE SEE NFPA-75, |
| | NEC 645.10 ETC. |
| | PLEASE NOTE ON PLANS, THAT ALL CONSTRUCTION |
| | REQUIREMENTS FOR "IT" ROOM MEET EXISTING CODE AS BEING |
| | SHOWN AS AN EXISTING "IT" ROOM, OR PROVIDE PERMIT |
| | NUMBER(S) FOR WHEN THIS WORK WAS PERMITTED. |
| | PLEASE ALSO EXPLAIN RATIONAL OF RECEPTS AND CIRCUITS |
| | OUTSIDE THE "IT" ROOM WHICH ARE BEING FED FROM THIS |
| | PANEL.??? |
| | PLANS AND WORK WHICH HAS , OR IS BEING DONE IS UNCLEAR. |
| | |
| | PLANS FOR THIS SCOPE AND SCOPE OF WORK RECENTLY APPLIED |
| | FOR SEEMS BE SUBMITTED IN A "PIECE MEAL" FASHION. |
| | |
| | 2) NOTE: PLEASE EXPLAIN NOTE FOR METERING. PLEASE SEE |
| | WORK BEING PROPOSED UNDER SEPARATE PERMIT HAS NOT |
| | COMMENCED OR PERMITTED AT THIS TIME. PLEASE VERIFY IF |
| | THIS IS ONE TENANT AND ONE METER , MAINS GROUPED |
| | ACCESSIBLE AND LOCATED FOR TENANT?? |
| | |
| | 3) NOTE: PLEASE KNOW AS PER FBC 2004 EXISTING AREAS |
| | BEING RENOVATED AND BRING SYSTEMS UP TO CODE SHALL BE |
| | CONSIDERED IN A ONE YEAR PERIOD OF TIME. |
| | |
| | |
| | ** PLEASE SUBMIT MORE INFORMATION AND EXPLANATION OF |
| | WORK. PLEASE SEE NOTES ABOVE FOR VERIFICATION OF |
| | EXISTING AS SHOWN CAN NOT BE VERIFIED MEETING CODE |
| | COMPLIANCE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |