2006-11-14 18:13:13BUILDING REVIEW CHECKLIST:
  
 1- ACCORDING TO INSTALLATION SCHEDULE SUBMITTED THE
 EDGE IS 3". NEED TO REDUCE ANCHOR SPACING ACCORDING TO
 TABLE ON SHEET 11 OF 14 OF ENGINEERED ACCORDION SHUTTER
 DRAWINGS. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712