| Plan Review Notes For Permit 06100956 |
| Permit Number |
06100956 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-10-05 15:32:21 | | | | *** DENIED REVISION *** | | | | | | | | | 1) NOTE: PLANS ARE NOW SHOWING A NEW SUB PANEL BEING | | | LISTED ON PANEL *B* HOWEVER THIS NEW SUB PANEL DOES NOT | | | EXIST ON RISER. | | | PLEASE SHOW WHERE THIS NEW PANEL IS. | | | PLEASE SEE THE PLANS INDICATE A J-BOX FOR CONNECTION OF | | | THESE NEW FEEDERS/BRANCH CIRCUITS YET THE LOCATION OF | | | THIS PANEL CAN NOT BE CONFIRMED. | | | PLEASE SEE THE PANEL SCHEDULE *B* DOES NOT INDICATE ANY | | | NEUTRAL CONDUCTOR WITH THE OTHER CONDUCTORS AS LISTED. | | | CLARIFY WHERE THE PREVIOUS 120V CIRCUITS NOW OBTAIN A | | | NEUTRAL IF NONE IS INSTALLED. | | | DOES THIS PANEL CONTAIN OVER CURRENT PROTECTION | | | DEVICES? | | | DOES THIS PANEL MEET THE MINIMUM CLEARANCE REQUIREMENTS | | | PER 110.26, 240.24? | | | DOES THIS PANEL MEET THE LOCATION FOR ITS ENVIRONMENT? | | | 110.3 | | | PLEASE SUBMIT THE PANEL SCHEDULE FOR THIS NEW CHEF | | | TABLE PANEL. | | | PLEASE SHOW LOCATION AND MEETING 110.26 | | | PLEASE PROVIDE LISTING FOR EQUIPMENT TO REVIEW. THIS | | | WILL NEED TO SHOW ALL ITEMS BEING FED/EQUIPMENT | | | SCHEDULE. 90.7, 110.3 | | | | | | FBC 106.1.2 | | | | | | IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS | | | REVIEW | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|