Plan Review Notes
Plan Review Notes For Permit 06100956
Permit Number 06100956
Review Stop E
Sequence Number 5
Notes
Date Text
2007-10-05 15:32:21 
 *** DENIED REVISION ***
  
  
 1) NOTE: PLANS ARE NOW SHOWING A NEW SUB PANEL BEING
 LISTED ON PANEL *B* HOWEVER THIS NEW SUB PANEL DOES NOT
 EXIST ON RISER.
 PLEASE SHOW WHERE THIS NEW PANEL IS.
 PLEASE SEE THE PLANS INDICATE A J-BOX FOR CONNECTION OF
 THESE NEW FEEDERS/BRANCH CIRCUITS YET THE LOCATION OF
 THIS PANEL CAN NOT BE CONFIRMED.
 PLEASE SEE THE PANEL SCHEDULE *B* DOES NOT INDICATE ANY
 NEUTRAL CONDUCTOR WITH THE OTHER CONDUCTORS AS LISTED.
 CLARIFY WHERE THE PREVIOUS 120V CIRCUITS NOW OBTAIN A
 NEUTRAL IF NONE IS INSTALLED.
 DOES THIS PANEL CONTAIN OVER CURRENT PROTECTION
 DEVICES?
 DOES THIS PANEL MEET THE MINIMUM CLEARANCE REQUIREMENTS
 PER 110.26, 240.24?
 DOES THIS PANEL MEET THE LOCATION FOR ITS ENVIRONMENT?
 110.3
 PLEASE SUBMIT THE PANEL SCHEDULE FOR THIS NEW CHEF
 TABLE PANEL.
 PLEASE SHOW LOCATION AND MEETING 110.26
 PLEASE PROVIDE LISTING FOR EQUIPMENT TO REVIEW. THIS
 WILL NEED TO SHOW ALL ITEMS BEING FED/EQUIPMENT
 SCHEDULE. 90.7, 110.3
  
 FBC 106.1.2
  
 IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS
 REVIEW
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]