Plan Review Notes
Plan Review Notes For Permit 06100956
Permit Number 06100956
Review Stop E
Sequence Number 3
Notes
Date Text
2007-03-24 16:30:26PLANS WERE REVIEW WHILE IN ZONING, PLANS REMAIN IN
 ZONING ON 3/24
2007-03-24 16:27:07*** UNSAT 3RD REVIEW **
 * FIRST REVIEW UNDER PERMIT.
  
  
 1) NOTE: PLEASE CLARIFY SHEETS 2 AND 3 OF THE FLORIDA
 ENERGY CALCULATIONS. PLEASE SEE THE FOLLOWING AS THEY
 DO NOT CORRELATE WITH THE ELECTRICAL PLANS.
  
 A) PLEASE SEE THAT THERE IS NOT EXTERIOR LIGHTING
 ENTERED AND PARKING EXTERNAL LIGHTING ON CALCULATIONS
 YET THE PLANS CONTAIN BOTH.
 B) PLEASE SEE THE BATH FIXTURES, WATTAGE AND CONTROLS
 DO NOT CORRELATE. THE INPUT DATA ONLY CONTAINS ONE
 FIXTURE OF EACH TYPE WHEN THERE ARE TWO FIXTURES OF
 EACH TYPE ON PLANS.(ONE OF EACH TYPE OF FIXTURE IN EACH
 BATH)
 PLEASE ALSO SEE THE TYPE OF CONTROL ENTERED IS
 *CENTRAL* WHICH IS NOT POSSIBLE WHEN THE PLANS DO NOT
 HAVE A *CENTRAL CONTROL*. PLANS DO INDICATE *OCCUPANCY
 SENSOR TYPE CONTROL*.
 C) PLEASE SEE DINING TYPE E WHICH STATES *CENTRAL
 CONTROL*, HOWEVER NO CENTRAL LIGHTING CONTROL SYSTEM IS
 PROVIDED. THIS TYPE OF FIXTURE IS WIRED AHEAD OF ANY
 CONTROLS OR SWITCHES PER 700.12E ANYWAY. PLEASE
 ADJUST.
 D) PLEASE SEE SIGNAGE IN KITCHEN AREA, SHOWS C-1 AS 17W
 AND 16W ON CALCULATIONS.
 E) PLEASE SEE KITCHEN EM TYPE FIXTURES WHICH INDICATE
 *CENTRAL CONTROL* FOR THESE ALSO. SAME AS NOTED ON *C*
 ABOVE.
  
 PLEASE COORDINATE. IF A LIGHTING SYSTEM IS BEING
 INSTALLED PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT
 ALL INFORMATION FOR SAID SYSTEM.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved