| 2007-02-17 13:23:34 | PAUL SCHMITZ |
| | [email protected] FBC 2004 PLUMBING |
| | CODE PLAN REVIEW |
| | FBC2004 FUEL GAS CODEPLAN REVIEW |
| | FBC 2004 CH 11, FL ACESSIBILITY CODE |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | |
| | DENIED,2ND PLAN |
| | REVIEW |
| | EACH PREVIOUS COMMENT,WILL BE ADDRESSED,AS OK OR |
| | DENIED. |
| | NEW COMMENTS ADDRESSED SEPARATELY. |
| | |
| | 1)OK |
| | |
| | 2) DENIED, PROVIDE LOCATION OF WORK AND STAMPED SHTS |
| | FROM DBPR |
| | PLANS SHALL BE ROUTED TO DBPR |
| | BUSINESS AND HOTEL DIVISION FOR |
| | REVIEW. MINIMUM 2 SETS OF PLANS |
| | SHALL BE REVIEWED AND STAMPED |
| | AND THE TWO PAGE ?WORKSHEETS? |
| | ATTACHED TO EACH SET OF PLANS |
| | PRIOR TO RESUBMITTING TO CITY OF WEST PALM BEACH FOR |
| | REVIEW. PLEASE CONTACT DBPR |
| | AT (850) 487-1395. |
| | |
| | 3)DENIED, SEE ATTACHED RESPONSE FROM WPBUD,DATED |
| | 12-26-06, 2-1250 GAL GREASE TANKS REQUIRED. |
| | SHT P 200, GREASE TRAP SIZE. TO BE CONFIRMED BY |
| | CONTACT W P BEACHWATERPLANT LAB SUPERVISOR |
| | INDUSTRIAL COORDINATOR, |
| | LYNN MASSON |
| | OFFICE 561-822-2271E-MAIL [email protected] |
| | |
| | 4)OK |
| | |
| | 5) DENIED, SHT P-100 PLUMBING ISOMETRIC SHOWS PIPING |
| | OVER HEAD. WITH DOWN FEED PIPE. |
| | SHT P-100 DETAIL 7PLUMBING ISOMETRIC |
| | SEC 606.1 LOCATION OF FULL-OPEN VALVES. |
| | FULL-OPEN VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | ONTHE TOP OF EVERY WATER DOWN-FEED PIPE IN OCCUPANCIES |
| | OTHER THAN ONE- AND TWO-FAMILY RESIDENTIAL |
| | OCCUPANCIES. |
| | |
| | 6)DENIED,SHT A-121, P-100; REFERENCES A DISHWASHER |
| | #48, THEREFORE QUICK OPENING VALE. |
| | SHT P100 SEC 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | |
| | 7) DENIED, NEW COMMENT |
| | SHT CS LISTS L-1, L -2 , L-3 IRRIGATION, NOT WITH THIS |
| | SET OF PLANS. |
| | SHT P- 100, 110 PLAN NOTES #1, #9 REFERENCE TO TO SITE |
| | UTILITY PLANS. |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| | 106.3.5). |
| | |
| | 8) OK |
| | |
| | END OF COMMENTS, QUESTIONS; 561-805-6692 |