Plan Review Notes
Plan Review Notes For Permit 06100956
Permit Number 06100956
Review Stop M
Sequence Number 2
Notes
Date Text
2007-02-16 09:11:43*FOR PLAN REVIEW ONLY, NOT FOR PERMIT*
 *** DENIED ***
 1) ONE SET OF THE ENERGY CALCULATIONS IS A PHOTO COPY,
 PLEASE SUBMIT TWO SIGNED AND SEALED SETS.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) AS REQUESTED IN LAST REVIEW 10-31-06. PLEASE SUBMIT
 COOLING LOAD CALCULATIONS, PER 2004 FBC
 13-407.1.ABC.1.
  
 4) PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED
 ROOF TOP CONDENSER UNIT STANDS, SEE FS 553.842 (1) AND
 FAC 9B-72.010 (31) (G).
 ** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) AS REQUESTED IN LAST REVIEW 10-31-06 NOTE #9. NEED
 DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT (WITH
 ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004 FBC
 1609). RESPONSEWAS SEE DETAIL "C"/S4 WHICH SHOWS RTU
 NOT MAU IF DETAIL IS FOR BOTH UNITS, PLEASE STATE SO IN
 THE DETAIL.
  
 6) AS NOTED IN LAST REVIEW 10-31-06 NOTE #10. SEE PAGE
 A-140 SHOWS ROOF TOP AIR HANDLER, PLANS HAVE NOT BEEN
 CORRECTED TO SHOW THE MAKE UP AIR UNIT, AS RESPONSE
 STATES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.