| 2007-02-16 09:11:43 | *FOR PLAN REVIEW ONLY, NOT FOR PERMIT* |
| | *** DENIED *** |
| | 1) ONE SET OF THE ENERGY CALCULATIONS IS A PHOTO COPY, |
| | PLEASE SUBMIT TWO SIGNED AND SEALED SETS. |
| | |
| | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| | ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 3) AS REQUESTED IN LAST REVIEW 10-31-06. PLEASE SUBMIT |
| | COOLING LOAD CALCULATIONS, PER 2004 FBC |
| | 13-407.1.ABC.1. |
| | |
| | 4) PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED |
| | ROOF TOP CONDENSER UNIT STANDS, SEE FS 553.842 (1) AND |
| | FAC 9B-72.010 (31) (G). |
| | ** PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) AS REQUESTED IN LAST REVIEW 10-31-06 NOTE #9. NEED |
| | DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT (WITH |
| | ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004 FBC |
| | 1609). RESPONSEWAS SEE DETAIL "C"/S4 WHICH SHOWS RTU |
| | NOT MAU IF DETAIL IS FOR BOTH UNITS, PLEASE STATE SO IN |
| | THE DETAIL. |
| | |
| | 6) AS NOTED IN LAST REVIEW 10-31-06 NOTE #10. SEE PAGE |
| | A-140 SHOWS ROOF TOP AIR HANDLER, PLANS HAVE NOT BEEN |
| | CORRECTED TO SHOW THE MAKE UP AIR UNIT, AS RESPONSE |
| | STATES. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |