| 2007-03-01 19:35:03 | *****DENIED***** |
| | |
| | |
| | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN |
| | REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | |
| | 1.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION |
| | CODE, THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED. |
| | LIST ON SHEET A000,FIRE CODE: 2004 FLORIDA FIRE |
| | PREVENTION CODE;LIFE SAFETY: 2003 NFPA 101 |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | PLEASE SHOW ON THE PLANS |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEROF.PLEASE SHOW ON THE PLANS |
| | |
| | 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE |
| | REMOVED FROM THE STRUCTURE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. |
| | PLEASE SHOW ON THE PLANS |
| | |
| | 5.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE |
| | ELEVATION WHICH FRONTS PALM BEACH LAKES BOULEVARD.AS |
| | PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS |
| | THAN 6" IN HEIGHT AND 1" IN WIDTH.DISPLAYED NUMERICAL |
| | ADDRESS SHALL BE ON THE STRUCTURE OF THE BUILDING, NOT |
| | THE DOOR OF THE BUILDING. |
| | |
| | 7.PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS |
| | AND CEILINGS IN EXITS AND EXIT ACCESS CORRIDORS. PLEASE |
| | SHOW ON THE PLANS |
| | |
| | 8.INCLUDE A LAYOUT OF THE EXISTING AND/OR NEW FIRE |
| | ALARM SYSTEM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH |
| | COMMENTWAS ADDRESSED |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |