Plan Review Notes
Plan Review Notes For Permit 06100956
Permit Number 06100956
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-04 19:55:52******* UNSAT 2ND REVIEW ******
  
 *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION
 AND/OR CHANGES MADE TO PLANS.
  
 **** IMPORTANT****
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*.
  
 A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY
 THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE
 PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE
 #1**
  
 B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A
 REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW
 NOTE WILL BE REMOVED.
  
 C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF
 THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL.
 THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS
 REVIEW NOTE #1**
  
 D) NEW NOTES WILL BE ADDED TO THE END AND LABELED **
 NEW NOTES **
  
  
  
  
  
 ** PLEASE KNOW THAT PLANS STILL HAVE NOT BEEN SUBMITTED
 FOR PERMIT APPLICATION ANS SINCE THE LAST REVIEW THE
 STATE OF FLORIDA HAS ADOPTED NEW CODES. PLANS HAVE BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN
 SUBMITTED FOR PERMIT.
 ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT, THEY
 ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS
 THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH
 CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT
 MAY CHANGE.
  
  
 1) NOTE:NO/OK, PLEASE SEE MOST OF THE PREVIOUS NOTE
 WAS ADDRESSED HOWEVER PLEASE SEE THE STATE OF FLORIDA
 HAS ADOPTED NEW CODES AND THE FOLLOWING SHALL BE
 STATED.
 2005 NFPA-70 NEC.
 PLANS INDICATE A 2004 NEC WHICH IS NOT VALID.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE THAT THE FOLLOWING CODES AT A MINIMUM SHALL
 BE STATED ON PLANS.
 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72
 ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA
 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE
 NFPA-70 WILL BE THE 2005.)
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK/NO, PLEASE SEE THE SIGN CIRCUITS WERE ADDED
 WHICH IS OK, HOWEVER PLEASE SEE THE LOAD ON THESE IS
 SHOWN AT 1500VA AND 10AMPS? PLEASE SEE 1500VA @120VOLTS
 IS 12.5. THIS COULD HAVE BEEN REDLINED, HOWEVER THE
 PLANS ARE NOT IN FOR PERMIT AND ARE COMING BACK FOR
 OTHER COMMENTS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN VA TO BE
 SHOWN FOR SIGN CIRCUIT. 1200 MIN.
  
 5) NOTE: OK.
  
 6) NOTE: OK, HOWEVER PLEASE SEE THE FOOTER IS BEING
 SHOWN FOR AN ATTACHMENT, PLEASE VERIFY IF EXISTING OR
 IS IT THE SPECIFICATION OF THE ENGINEER FOR THE
 EXISTING FOOTER TO BE *CHIPPED* INTO TO OBTAIN THIS
 CONNECTION IF NOT EXISTING?
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM DETAIL.
 STATING CODE COMPLIANCE IN LIEU OF DETAIL IS NOT
 PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS KNOWN
 TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING AND
 THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A
 MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS
 REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS
 LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50,
 250.56 250.104 ETC.
  
 7) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS
 INFORMATION WAS SUBMITTED IN PACKAGE HOWEVER THIS COULD
 NOT BE LOCATED.
 PLEASE SEE TWO SEPARATE ELECTRICAL SITE PLANS WERE
 SUBMITTED SHOWING TWO SEPARATE PHOTO-METRICS ETC.
 PLEASE SEE TWO SEPARATE DESIGN PROFESSIONALS ALSO.
 PLEASE SEE THAT THE PLANS SHALL STATE THE MINIMUM 2004
 FBC WIND LOAD OF 140MPH (3 SECOND GUST) EVEN IF THE
 CALCULATIONS ARE SEPARATE. PLEASE KNOW THAT IF THE
 POLES ARE NOT ORDERED AND OBTAINED AT THE TIME OF
 PERMIT APPLICATION THE CALCULATIONS CAN BE A *PROVISO*
 AS LONG AS THE PLANS INDICATE THE CORRECT INFORMATION.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW LT POLES.
 PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT AREA) OF
 LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS WHICH WILL
 BE REQUIRED TO BE SIGNED, DATED AND SEALED BY A FLORIDA
 PE. PLEASE ALSO BE SURE THE TITLE BLOCK FOR THE DESIGN
 PROFESSIONAL IS ON PLANS.
  
 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL
 SCHEDULES. 310.16,240.4,
 FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH.
 106.1.2
 PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION
 AT THIS TIME.
  
  
 ** NEW NOTES **
  
 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGN
 PROFESSIONAL. PLEASE SEE THE CALCULATIONS SUBMITTED ARE
 PHOTO-COPIES OF SIGNED AND SEALED ONES.
 PLEASE SEE FS 471.025, FAC 61G15-23.002 AND FBC
 13-103.1.1.1
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]