| 2007-02-04 19:55:52 | ******* UNSAT 2ND REVIEW ****** |
| | |
| | *** PLEASE SEE THERE ARE ITEMS FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW |
| | COMMENTS BASED ON CHANGES IN PLANS AND NEW INFORMATION |
| | AND/OR CHANGES MADE TO PLANS. |
| | |
| | **** IMPORTANT**** |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | THE PREVIOUS REVIEW WITH A *NO*, *OK* OR *NO/OK*. |
| | |
| | A) A, NO WILL CONTAIN A FURTHER EXPLANATION AS TO WHY |
| | THE COMMENT MAY NOT HAVE BEEN FULLY ADDRESSED WITH THE |
| | PREVIOUS REVIEW NOTE BELOW WITH **PREVIOUS REVIEW NOTE |
| | #1** |
| | |
| | B) A, OK, WILL HAVE NO COMMENTS EXCEPT PERHAPS A |
| | REFERENCE TO SEE ** NEW NOTES*. THE PREVIOUS REVIEW |
| | NOTE WILL BE REMOVED. |
| | |
| | C) A, NO/OK, WILL HAVE FURTHER EXPLANATION AS PART OF |
| | THE COMMENT MAY HAVE BEEN ADDRESSED, HOWEVER NOT ALL. |
| | THE PREVIOUS REVIEW NOTE WILL BE NOTED **PREVIOUS |
| | REVIEW NOTE #1** |
| | |
| | D) NEW NOTES WILL BE ADDED TO THE END AND LABELED ** |
| | NEW NOTES ** |
| | |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW THAT PLANS STILL HAVE NOT BEEN SUBMITTED |
| | FOR PERMIT APPLICATION ANS SINCE THE LAST REVIEW THE |
| | STATE OF FLORIDA HAS ADOPTED NEW CODES. PLANS HAVE BEEN |
| | SUBMITTED FOR "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN |
| | SUBMITTED FOR PERMIT. |
| | ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT, THEY |
| | ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS |
| | THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH |
| | CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT |
| | MAY CHANGE. |
| | |
| | |
| | 1) NOTE:NO/OK, PLEASE SEE MOST OF THE PREVIOUS NOTE |
| | WAS ADDRESSED HOWEVER PLEASE SEE THE STATE OF FLORIDA |
| | HAS ADOPTED NEW CODES AND THE FOLLOWING SHALL BE |
| | STATED. |
| | 2005 NFPA-70 NEC. |
| | PLANS INDICATE A 2004 NEC WHICH IS NOT VALID. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE THAT THE FOLLOWING CODES AT A MINIMUM SHALL |
| | BE STATED ON PLANS. |
| | 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72 |
| | ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA |
| | 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE |
| | NFPA-70 WILL BE THE 2005.) |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK/NO, PLEASE SEE THE SIGN CIRCUITS WERE ADDED |
| | WHICH IS OK, HOWEVER PLEASE SEE THE LOAD ON THESE IS |
| | SHOWN AT 1500VA AND 10AMPS? PLEASE SEE 1500VA @120VOLTS |
| | IS 12.5. THIS COULD HAVE BEEN REDLINED, HOWEVER THE |
| | PLANS ARE NOT IN FOR PERMIT AND ARE COMING BACK FOR |
| | OTHER COMMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN VA TO BE |
| | SHOWN FOR SIGN CIRCUIT. 1200 MIN. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK, HOWEVER PLEASE SEE THE FOOTER IS BEING |
| | SHOWN FOR AN ATTACHMENT, PLEASE VERIFY IF EXISTING OR |
| | IS IT THE SPECIFICATION OF THE ENGINEER FOR THE |
| | EXISTING FOOTER TO BE *CHIPPED* INTO TO OBTAIN THIS |
| | CONNECTION IF NOT EXISTING? |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM DETAIL. |
| | STATING CODE COMPLIANCE IN LIEU OF DETAIL IS NOT |
| | PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS KNOWN |
| | TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING AND |
| | THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A |
| | MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS |
| | REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS |
| | LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50, |
| | 250.56 250.104 ETC. |
| | |
| | 7) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS |
| | INFORMATION WAS SUBMITTED IN PACKAGE HOWEVER THIS COULD |
| | NOT BE LOCATED. |
| | PLEASE SEE TWO SEPARATE ELECTRICAL SITE PLANS WERE |
| | SUBMITTED SHOWING TWO SEPARATE PHOTO-METRICS ETC. |
| | PLEASE SEE TWO SEPARATE DESIGN PROFESSIONALS ALSO. |
| | PLEASE SEE THAT THE PLANS SHALL STATE THE MINIMUM 2004 |
| | FBC WIND LOAD OF 140MPH (3 SECOND GUST) EVEN IF THE |
| | CALCULATIONS ARE SEPARATE. PLEASE KNOW THAT IF THE |
| | POLES ARE NOT ORDERED AND OBTAINED AT THE TIME OF |
| | PERMIT APPLICATION THE CALCULATIONS CAN BE A *PROVISO* |
| | AS LONG AS THE PLANS INDICATE THE CORRECT INFORMATION. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW LT POLES. |
| | PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT AREA) OF |
| | LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS WHICH WILL |
| | BE REQUIRED TO BE SIGNED, DATED AND SEALED BY A FLORIDA |
| | PE. PLEASE ALSO BE SURE THE TITLE BLOCK FOR THE DESIGN |
| | PROFESSIONAL IS ON PLANS. |
| | |
| | 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL |
| | SCHEDULES. 310.16,240.4, |
| | FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH. |
| | 106.1.2 |
| | PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION |
| | AT THIS TIME. |
| | |
| | |
| | ** NEW NOTES ** |
| | |
| | 9) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE |
| | REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGN |
| | PROFESSIONAL. PLEASE SEE THE CALCULATIONS SUBMITTED ARE |
| | PHOTO-COPIES OF SIGNED AND SEALED ONES. |
| | PLEASE SEE FS 471.025, FAC 61G15-23.002 AND FBC |
| | 13-103.1.1.1 |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT THE ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |