| 2007-03-02 10:55:55 | BUILDING PLAN REVIEW |
| | PERMIT: 06100956 |
| | ADD: 2380 PALM BCH LAKES BLVD |
| | CONT:""PLAN REVIEW"" |
| | TEL: (407)645-5008 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | |
| | 2004 BUILDING PLAN REVIEW |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3)2ND REQUEST, RESPONSE INDICATES SHEET S-1 G-3 STATES |
| | ADJACENT |
| | ONSITE FACILITIES, STRUCTURES & UTILITY LINES NO |
| | MENTION OF |
| | ADVERSELY IMPACT OF ADJACENT PROPERTY WHICH INCLUDES |
| | BUT NOT LIMITED TO THE CONTROL OF DUST, NOISE, WATER |
| | DEBRIS |
| | AND THE STORAGE OF CONSTRUCTION MATERIAL. 109.3.10* |
| | IMPACT OF CONSTRUCTION. |
| | ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERMORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS |
| | SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| | BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| | DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY |
| | SHALL NOT ADVERSELY IMPACT HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) 2ND REQUEST,5C TYPE OF CONSTRUCTION AS DEFINED IN |
| | CHAPTER 6 TABLE 601/ |
| | RESPONSE IS TYPE II BUILDING, DOES THIS MEAN |
| | THAT YOU WANT TO DESIGNTO THE MORE RESTRICTIVE TYPE |
| | II REQUIREMENTS? |
| | THIS BUILDING BEING A A-2 OCCUPANCY, MINIMUM BUILDING |
| | TYPE OF V-B WITH 6,000 SQ FT / 1 STORY. |
| | |
| | 6) 2ND REQUEST, PLEASE SUBMIT REPORT PRODUCED BY |
| | GEOSYNTEC CONSULANTS 5/01/06 |
| | FBC 1802.2.1 QUESTIONABLE SOILS, |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 7) COMPLIED WITH SUBMITTALS PROVIDED, MISSING |
| | SUBMITTALS. |
| | |
| | 8) COMPLIED, NEW CONSTRUCTION. |
| | |
| | 9) COMPLIED. |
| | |
| | 10A) SHEET S-1 DESIGN CRITERIA,D-1 STATES ASCE 7-?? |
| | DOES NOT PROVIDE THE EDITION? |
| | |
| | 10B) ROOF ZONE 3 THE TRTIBUTARY AREA OF THE FASTENER IS |
| | LESS THAN 10 SQ FT THE NEGATIVE PRESSURES REQUIRED TO |
| | HOLD THE SYSTEM DOWN IS -89.0. |
| | |
| | 11) 2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | MISSING REPORTS: |
| | D) EXTERIOR METAL DOOR |
| | F ) LOUVERS |
| | G) TRUSS ANCHOR FOR THE METALC CHANNELS |
| | I) ROOFING ASSEMBLIES FLAT ROOF AS WELL AS THE METAL |
| | CANOPY |
| | |
| | 11B) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | NEW COMMENT |
| | 12)ENERGY CALCS PLEASE PROVIDE 2 ORIGINAL SIGNED AND |
| | SEALED ENERGY REPORTS |
| | PLEASE HAVE THE OWNER/ AGENT SIGN THE ENERGY |
| | CALCULATIONS. |
| | |
| | SINCE THIS IS A DEMO AND NEW STURCTURE REVIEW BY P.B. |
| | COUNTY IMPACT FEE OFFICE WILL BE REQUIRED. |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |