2007-03-02 10:55:55BUILDING PLAN REVIEW
 PERMIT: 06100956
 ADD: 2380 PALM BCH LAKES BLVD
 CONT:""PLAN REVIEW""
 TEL: (407)645-5008
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
 2004 BUILDING PLAN REVIEW
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)2ND REQUEST, RESPONSE INDICATES SHEET S-1 G-3 STATES
 ADJACENT
 ONSITE FACILITIES, STRUCTURES & UTILITY LINES NO
 MENTION OF
 ADVERSELY IMPACT OF ADJACENT PROPERTY WHICH INCLUDES
 BUT NOT LIMITED TO THE CONTROL OF DUST, NOISE, WATER
 DEBRIS
 AND THE STORAGE OF CONSTRUCTION MATERIAL. 109.3.10*
 IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 4) COMPLIED.
  
 5) 2ND REQUEST,5C TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 6 TABLE 601/
 RESPONSE IS TYPE II BUILDING, DOES THIS MEAN
 THAT YOU WANT TO DESIGNTO THE MORE RESTRICTIVE TYPE
 II REQUIREMENTS?
 THIS BUILDING BEING A A-2 OCCUPANCY, MINIMUM BUILDING
 TYPE OF V-B WITH 6,000 SQ FT / 1 STORY.
  
 6) 2ND REQUEST, PLEASE SUBMIT REPORT PRODUCED BY
 GEOSYNTEC CONSULANTS 5/01/06
 FBC 1802.2.1 QUESTIONABLE SOILS,
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) COMPLIED WITH SUBMITTALS PROVIDED, MISSING
 SUBMITTALS.
  
 8) COMPLIED, NEW CONSTRUCTION.
  
 9) COMPLIED.
  
 10A) SHEET S-1 DESIGN CRITERIA,D-1 STATES ASCE 7-??
 DOES NOT PROVIDE THE EDITION?
  
 10B) ROOF ZONE 3 THE TRTIBUTARY AREA OF THE FASTENER IS
 LESS THAN 10 SQ FT THE NEGATIVE PRESSURES REQUIRED TO
 HOLD THE SYSTEM DOWN IS -89.0.
  
 11) 2ND REQUEST, FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 MISSING REPORTS:
 D) EXTERIOR METAL DOOR
 F ) LOUVERS
 G) TRUSS ANCHOR FOR THE METALC CHANNELS
 I) ROOFING ASSEMBLIES FLAT ROOF AS WELL AS THE METAL
 CANOPY
  
 11B) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT
 12)ENERGY CALCS PLEASE PROVIDE 2 ORIGINAL SIGNED AND
 SEALED ENERGY REPORTS
 PLEASE HAVE THE OWNER/ AGENT SIGN THE ENERGY
 CALCULATIONS.
  
 SINCE THIS IS A DEMO AND NEW STURCTURE REVIEW BY P.B.
 COUNTY IMPACT FEE OFFICE WILL BE REQUIRED.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  