| 2007-10-15 11:26:22 | BUILDING PLAN REVIEW |
| | PERMIT: 06100956 |
| | ADD: 2380 PALM BCH LAKES BLVD |
| | CONT: COLUMBIA CONSTRUCTION |
| | TEL: (321)246-4825 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION NO.12 8/16/07REVIEW |
| | ACTION: DENIED |
| | |
| | SHEETS A.300, A.305 & A.315DENIED. THIS BUILDING IS |
| | CLASSIFIED AS A TYPE II-B, UNPROTECTED, UNSPRINKLED. |
| | THE SHEETS LISTED ABOVE NOW INDICATE THE USE OF 5/8" |
| | CDX PLYWOOD FOR SHEATHING ON BEARING WALLS WHEN |
| | REVIEWING SECTION 603.1 AND TABLE 603 FOR A TYPE II-B |
| | STRUCTURE THERE CAN BE NO PLYWOOD SHEATHING FOR A II-B |
| | BUILDING. |
| | HOWEVER THIS IS THE DESIGN THAT YOU ELECTED TO USE, THE |
| | MINIMUM BUILDING TYPE BY CODE IS A TYPE V-B FOR A A-2 |
| | OCCUPANCY GROUPWITH AN ALLOWABLE 6000 SQ FT/ SINGLE |
| | STORY. |
| | |
| | IF THIS BUILDING WAS TO BE DECLARED A TYPE V-B BUILDING |
| | AND TO USE PLYWOOD SUBSHEATHING THEREWOULD STILL BE |
| | CONCERNS IN AREAS WHERE THE SHEATHING WOULD BE WITHIN |
| | SIX INCHES OF GRADE. PLEASE REVIEW 2304.11.2.5 FOR WOOD |
| | SUBSHEATHING REQUIREMENTS. |
| | |
| | THE ORIGINAL PLANS WERE ALSO PULLED TO SEE IF THERE HAD |
| | BEEN REFRENCE MADE TO THE USE OF WOOD SUBSHEATHING OR |
| | POSSIBLE DENSE-GLASS SINCE THERE IS TO BE AN EFIS |
| | FINISH SYSTEM. I HADN'T FOUND ANY PRODUCT APPROVALS FOR |
| | THE EFIS WALL SYSTEMS. |
| | A BUILDING PROVISO # 1 WASISSUED WITH THE ISSUANCE |
| | OF THE PLANS: |
| | 1) PLEASE PROVIDE PRODUCT APPROVAL REPORT FOR STO CORP. |
| | THE FLORIDA COVER SHEET INDICATE THE CORRESPONDING |
| | REPORT TO BE A ES REPORT NOT THE SUBMITTED MIAMI-DADE |
| | NOA. |
| | PLEASE INDICATE WHICH SUB-SYSTEM WILL BE USED IN |
| | CONJUCTION WITH THIS PROJECT. WILL BE REQUIRED WITHIN |
| | 30 DAYS OF ISSUANCE. |
| | TO DATE NO PRODUCT APPROVALS HAVE BEEN SUBMITTED AND |
| | THIS ISSUE STILL REMAINS AS "OPEN". |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | |
| | |
| | |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |