| Plan Review Notes For Permit 06100956 |
| Permit Number |
06100956 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-31 14:21:32 | *FOR PLAN REVIEW ONLY, NOT FOR PERMIT* | | | *** DENIED *** | | | 1) ENGINEERING FIRM'S CERTIFICATE OF AUTHORIZATION | | | NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC | | | 61G15-23.002. | | | | | | 2) THE ENGINEER RICHARD JONES PRINTED NAME AND LICENSE | | | NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC | | | 61G15-23.002. | | | | | | 3) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC | | | 13-101.1.3. | | | | | | 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004 | | | FBC 13-407.1.ABC.1. | | | | | | 5) PLEASE SHOW OUTDOOD AIR CALCULATIONS ON MECHANICAL | | | PLANS, PER 2004 FBC/M 403.2. | | | | | | 6) PLEASE SHOW A/C SYSTEM'S SEER OR EER ON EQUIPMENT | | | SCHEDULE. | | | | | | 7) NEED DETAIL FOR HANGING KITCHEN HOOD TO ROOF | | | STRUCTURE. | | | | | | 8) NEED DETAIL FOR SECURING COOLER CONDENSER UNIT AND | | | STAND, TO ROOF, TO WITHSTAND 140 MPH WINDS, PER 2004 | | | FBC 1609. | | | | | | 9) NEED DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT | | | (WITH ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004 | | | FBC 1609). | | | | | | 10) SEE PAGE A-140 SHOWS ROOF TOP AIR HANDLER, MECH. | | | PLANS DO NOT LIST A ROOF TOP AIR HANDLER, DO YOU MEAN | | | THE MEKE UP AIR UNIT, PLEASE EXPLAIN OR CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|