2006-10-31 14:21:32*FOR PLAN REVIEW ONLY, NOT FOR PERMIT*
 *** DENIED ***
 1) ENGINEERING FIRM'S CERTIFICATE OF AUTHORIZATION
 NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC
 61G15-23.002.
  
 2) THE ENGINEER RICHARD JONES PRINTED NAME AND LICENSE
 NUMBER MUST APPEAR IN THE TITLE BLOCK, PER FAC
 61G15-23.002.
  
 3) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.1.3.
  
 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 5) PLEASE SHOW OUTDOOD AIR CALCULATIONS ON MECHANICAL
 PLANS, PER 2004 FBC/M 403.2.
  
 6) PLEASE SHOW A/C SYSTEM'S SEER OR EER ON EQUIPMENT
 SCHEDULE.
  
 7) NEED DETAIL FOR HANGING KITCHEN HOOD TO ROOF
 STRUCTURE.
  
 8) NEED DETAIL FOR SECURING COOLER CONDENSER UNIT AND
 STAND, TO ROOF, TO WITHSTAND 140 MPH WINDS, PER 2004
 FBC 1609.
  
 9) NEED DETAIL FOR ROOF TOP KITCHEN HOOD MAKE-UP UNIT
 (WITH ANCHORING TO WITHSTAND 140 MPH WINDS, PER 2004
 FBC 1609).
  
 10) SEE PAGE A-140 SHOWS ROOF TOP AIR HANDLER, MECH.
 PLANS DO NOT LIST A ROOF TOP AIR HANDLER, DO YOU MEAN
 THE MEKE UP AIR UNIT, PLEASE EXPLAIN OR CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.