2006-12-21 13:49:25*****DENIED*****
  
  
  
 1.IN ADDITION TO THE 2004 FLORIDA FIRE PREVENTION
 CODE, THE 2003 EDITION OF NFPA 101 SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEROF.
  
 4.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 5.DISPLAY THE NUMERICAL ADDRESS ON THE APPROPIATE
 ELEVATION WHICH FRONTS PALM BEACH LAKES BOULEVARD.AS
 PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND 1" IN WIDTH.
  
 6.PROVIDE FLAME RETARDIBILITY INFORMATION FOR THE
 CANOPY.
  
 7.PROVIDE INTERIOR FINISH CLASSIFICATION FOR WALLS
 AND CEILINGS IN EXITS AND EXIT ACCESS CORRIDORS.
  
 8.INCLUDE A LAYOUT OF THE EXISTING FIRE SPRINKLER
 AND/OR FIRE ALARM SYSTEM DEVICES.HOW WILL THEY BE
 AFFECTED BY THE SCOPE OF WORK?
  
 9.IF THE FIRE PROTECTION SYSTEMS ARE MODIFIED DUE TO
 THE SCOPE OF WORK, SEPARATE PERMIT AND PLANS WILL BE
 REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  