| 2006-11-04 16:59:23 | *** UNSAT *** |
| | |
| | |
| | ** PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN SUBMITTED FOR |
| | PERMIT. |
| | ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT , THEY |
| | ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS |
| | THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH |
| | CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT |
| | MAY CHANGE. |
| | PLEASE KNOW, THE NFPA-70 WILL BE CHANGING AND THE 2005 |
| | MAY BE ADOPTED BY THE STATE IN THE NEXT COUPLE OF |
| | MONTHS. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES AT A |
| | MINIMUM SHALL BE STATED ON PLANS. |
| | 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72 |
| | ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA |
| | 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE |
| | NFPA-70 WILL BE THE 2005.) |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR ENGINEERING FIRM AND ENGINEER OF |
| | RECORD PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002. |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | OF ENGINEER AND MISSING THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR FIRM. |
| | PLEASE SEE FLORIDA STATUTES 471.023. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | PLEASE ALSO SEE FRONT COVER SHEET. |
| | |
| | 3) NOTE: PLEASE SEE 210.62 FOR SPACING OF WINDOW |
| | RECEPTS. PLEASE ALSO SEE 220.12A FOR LOAD WHICH IS |
| | REQUIRED TO BE SHOWN IN THE BREAK DOWN OF THE LOAD |
| | CALCULATIONS SUBMITTED. |
| | PLEASE SEE PLANS, PER SCALE APPEAR TO HAVE A COUPLE |
| | MISSING. |
| | |
| | 4) NOTE: PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN |
| | VA TO BE SHOWN FOR SIGN CIRCUIT. 1200 MIN. |
| | |
| | 5) NOTE: PLEASE SEE RISER SHOWS AN "EQUIPMENT GROUNDING |
| | CONDUCTOR" FROM THE METER TO THE MAIN DISCONNECT. |
| | PLEASE 250.6, AND 250.24B AS THIS EQUP GRND IS ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 6) NOTE: PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM |
| | DETAIL. STATING CODE COMPLIANCE IN LIEU OF DETAIL IS |
| | NOT PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS |
| | KNOWN TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING |
| | AND THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A |
| | MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS |
| | REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS |
| | LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50, |
| | 250.56 250.104 ETC. |
| | |
| | 7) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW |
| | LT POLES. PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT |
| | AREA) OF LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS |
| | WHICH WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED |
| | BY A FLORIDA PE. PLEASE ALSO BE SURE THE TITLE BLOCK |
| | FOR THE DESIGN PROFESSIONAL IS ON PLANS. |
| | |
| | 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL |
| | SCHEDULES. 310.16,240.4, |
| | FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH. |
| | 106.1.2 |
| | PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION |
| | AT THIS TIME. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT THE ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-11-04 16:14:09 | REVIEW IN PROGRESS |
| 2006-11-03 20:56:23 | IN ELEC FOR REVIEW. |