Plan Review Notes
Plan Review Notes For Permit 06100956
Permit Number 06100956
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-04 16:59:23*** UNSAT ***
  
  
 ** PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR
 "PLAN REVIEW" ONLY AND HAVE NOT YET BEEN SUBMITTED FOR
 PERMIT.
 ** PLEASE KNOW, EVEN IF PLANS ARE CODE COMPLIANT , THEY
 ARE NOT STAMPED UNTIL PERMIT HAS BEEN APPLIED FOR AS
 THE VALUE FOR THE SCOPE OF WORK IS VERIFIED ALONG WITH
 CODES IN EFFECT ATTHE TIME OF APPLICATION FOR PERMIT
 MAY CHANGE.
 PLEASE KNOW, THE NFPA-70 WILL BE CHANGING AND THE 2005
 MAY BE ADOPTED BY THE STATE IN THE NEXT COUPLE OF
 MONTHS.
  
  
  
 1) NOTE: PLEASE SEE THAT THE FOLLOWING CODES AT A
 MINIMUM SHALL BE STATED ON PLANS.
 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 NFPA-72
 ** PLEASE SEE PLANS ON FRONT COVER SHEET REFLECT A NFPA
 2004. (PLEASE KNOW THE NEXT ADOPTED EDITION OF THE
 NFPA-70 WILL BE THE 2005.)
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR ENGINEERING FIRM AND ENGINEER OF
 RECORD PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF ENGINEER AND MISSING THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR FIRM.
 PLEASE SEE FLORIDA STATUTES 471.023.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE ALSO SEE FRONT COVER SHEET.
  
 3) NOTE: PLEASE SEE 210.62 FOR SPACING OF WINDOW
 RECEPTS. PLEASE ALSO SEE 220.12A FOR LOAD WHICH IS
 REQUIRED TO BE SHOWN IN THE BREAK DOWN OF THE LOAD
 CALCULATIONS SUBMITTED.
 PLEASE SEE PLANS, PER SCALE APPEAR TO HAVE A COUPLE
 MISSING.
  
 4) NOTE: PLEASE SEE 600.5 AND 220.3(B)(6) FOR THE MIN
 VA TO BE SHOWN FOR SIGN CIRCUIT. 1200 MIN.
  
 5) NOTE: PLEASE SEE RISER SHOWS AN "EQUIPMENT GROUNDING
 CONDUCTOR" FROM THE METER TO THE MAIN DISCONNECT.
 PLEASE 250.6, AND 250.24B AS THIS EQUP GRND IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISCONNECT.
  
 6) NOTE: PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM
 DETAIL. STATING CODE COMPLIANCE IN LIEU OF DETAIL IS
 NOT PERMITTED. PLEASE SEE MINIMUM PER 250.50. IT IS
 KNOWN TO THIS OFFICE THAT THIS IS AN EXISTING BUILDING
 AND THE FOOTER STEEL MAY NOT BE AVAILABLE. HOWEVER A
 MINIMUM OF 2-GRND RODS, COLD WATER AND BLDG STEEL IS
 REQUIRED. PLEASE ALSO INDICATE THE BONDING OF THE GAS
 LINE ON THE SECONDARY OF ANY UTILITY METER. 250.50,
 250.56 250.104 ETC.
  
 7) NOTE: PLEASE SUBMIT WIND LOAD CALCULATIONS FOR NEW
 LT POLES. PLEASE BE SURE THE EPA ( EFFECTIVE PROJECT
 AREA) OF LIGHT FIXTURES ARE REFLECTED ON CALCULATIONS
 WHICH WILL BE REQUIRED TO BE SIGNED, DATED AND SEALED
 BY A FLORIDA PE. PLEASE ALSO BE SURE THE TITLE BLOCK
 FOR THE DESIGN PROFESSIONAL IS ON PLANS.
  
 8) NOTE: PLEASE INDICATE ALL CONDUCTOR SIZES ON PANEL
 SCHEDULES. 310.16,240.4,
 FBC ADMIN SECT AS ADOPTED PER CITY OF WEST PALM BEACH.
 106.1.2
 PLEASE SEE NOTE # 7 FOR ANY VOLTAGE DROP CONSIDERATION
 AT THIS TIME.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  