| Date |
Text |
| 2006-11-16 14:56:16 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | MUNICIPAL CODE |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE FOLLOWING INFORMATION |
| | IS REQUIRED: THE CERTIFICATE OF AUTHORIZATION, |
| | (BUSINESS NUMBER), AND THE PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT. FAC 61G1-16.004(2)(6) & FS |
| | 481.219, 481.2055. (SEE ATTACHED SHEET FROM DBPR |
| | WEBSITE). (ALSO SEE ELECTRICAL REVIEW ON THE SUBJECT). |
| | |
| | 2. ALL PME SHEETS. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND LICENSE UMBER ON EACH SHEET, |
| | AND IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING |
| | BUSINESS, ENGINEERS SHALL, AS WELL, INDICATE THE NAME |
| | ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) |
| | & FS 471.025. |
| | |
| | 3. SHT P1.0 MISC. PLUMBING FIXTURES. THE REVERSE |
| | OSMOSIS FILTER SHALL BE NSF-58, OR WQAS S-300 |
| | COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATIONS |
| | INDICATING COMPLIANCE. SECTION 611.2. |
| | |
| | 4. SHT P2.0 SUPPLY PIPING WATER SYSTEM. A BACKFLOW |
| | PREVENTER IS REQUIRED ON THE ICE MACHINE AS WELL AS A |
| | WATER HAMMER ARRESTOR. SECTIONS 608.3 & 604.9.-A |
| | WATER HAMMER ARRESTOR IS REQUIRED ON THE DISHWASHER. |
| | SECTION 604.9.-FULL OPEN VALVES ARE REQUIRED ON ALL |
| | WATER DOWN-FEED PIPES. SECTION 606.1(4). |
| | |
| | 5. SHT P2.0 KEYED PLAN NOTES 16 & 19 WERE NOT LOCATED |
| | ON THE PLUMBING SUPPLY PLAN. PLEASE CLARIFY. SECTION |
| | 106.1.1.-NOTE 23 IS SHOWN TWICE ON THE FLOOR PLAN. |
| | THIS IS NOT REFLECTED IN THE RISER DIAGRAM. PLEASE |
| | CORRELATE RISER & FLOOR PLAN. SECTION 106.1.1.-NOTE |
| | 28 RPZV BACKFLOW REQUIRED. MAXIMUM 4' ABOVE THE FLOOR |
| | FOR TESTING & CERTIFICATION. SHOW ON PLAN. SECTION |
| | 106.1.1. |
| | |
| | 6. SHT P3.0 WASTE VENT RISER DIAGRAM. SUBMIT THE RISER |
| | DIAGRAM IN AN ISOMETRIC FORM THAT REFLECT THE FLOOR |
| | PLAN. SECTION 106.1.3.-A TRAP IS REQUIRED FOR THE |
| | FLOOR DRAIN. SECTION 1002.1.-A 4" AIR GAP IS |
| | REQUIRED FOR THE 3 COMPARTMENT SINK, AND A 2-1/2" AIR |
| | GAP IS REQUIRED FOR THE DISHWASHER. SECTION 80.2.1. |
| | |
| | 7. SHT P3.0 PLAN KEY NOTE 14 & THE PLUMBING WASTE/DRAIN |
| | PLAN RISER DIAGRAM. THE GREASE TRAP IS NOT APPROVED IN |
| | THE SPACE. ALL GREASE TRAPS ARE TO BE SIZED BY THE |
| | UTILITY DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT |
| | LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER BY PHONE |
| | (561) 822-2271, BY FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. UTILITY ORD. 3434. |
| | |
| | 8. SHT P4.0 DETAIL 5. DIELECTRIC UNIONS ARE NOT |
| | APPROVED FOR THE POTABLE WATER SYSTEM. USE A DIELECTRIC |
| | NIPPLE OR DIELECTRIC COUPLING. |
| | |