2006-11-02 11:06:38*** DENIED ***
 1) THE ARCHITECT FIRM'S LICENSE NUMBER MUST ALSO APPEAR
 IN THE TITLE BLOCK, PER FAC 61G-16.004.
  
 2) THE ENGINEER"S NAME, ADDRESS, AND LICENSE NUMBER
 MUST APPEAR IN THE TITLE BLOCK, PER FAC 61G15-23.002.
  
 3) IT APPEARS THAT THE SPACE ABOVE THE CEILING IS AN
 OPEN RETURN AIR PLENUM, AS THEIR IS NO RETURN AIR DUCT
 WORK SHOWING, IF SO PLEASE NOTE ON PLANS,MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
 HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84. PER 2004 FBC/M 602.2.1.
 IF NOT PLEASE CORRECT.
  
 4) SEE PLANS PAGE M1.0, CODES, PLEASE REFER TO THE 2004
 FBC.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.