| Plan Review Notes For Permit 06100955 |
| Permit Number |
06100955 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-02 11:06:38 | *** DENIED *** | | | 1) THE ARCHITECT FIRM'S LICENSE NUMBER MUST ALSO APPEAR | | | IN THE TITLE BLOCK, PER FAC 61G-16.004. | | | | | | 2) THE ENGINEER"S NAME, ADDRESS, AND LICENSE NUMBER | | | MUST APPEAR IN THE TITLE BLOCK, PER FAC 61G15-23.002. | | | | | | 3) IT APPEARS THAT THE SPACE ABOVE THE CEILING IS AN | | | OPEN RETURN AIR PLENUM, AS THEIR IS NO RETURN AIR DUCT | | | WORK SHOWING, IF SO PLEASE NOTE ON PLANS,MATERIALS | | | EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL | | | HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED | | | IN ACCORDANCE WITH ASTM E 84. PER 2004 FBC/M 602.2.1. | | | IF NOT PLEASE CORRECT. | | | | | | 4) SEE PLANS PAGE M1.0, CODES, PLEASE REFER TO THE 2004 | | | FBC. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|