Plan Review Notes
Plan Review Notes For Permit 06100955
Permit Number 06100955
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-20 15:16:41*****DENIED*****
  
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 3.INDICATE ON APPROPRIATE ELEVATION FRONT THE SUITE
 NUMBER FOR THIS TENANT SPACE.BE ADVISED THAT THE
 NUMBER IS TO BE VISIBLE BEFORE, DURING, AND AFTER
 CONSTRUCTION/DEMOLITION OPERATIONS.
  
 4.INTERIOR FINISH FOR WALLS AND CEILING SHALL BE
 CLASS "A" OR CLASS "B".
  
 5.IF THE FIRE SPRINKLER AND (OR) FIRE ALARM SYSTEM IS
 TO BE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS
 AND PERMIT ARE REQUIRED.
  
 6.IN REGARDS TO FIRE SPRINKLER COVERAGE, NFPA 13 -
 2002 EDITION - SHALL BE REFERENCED.(MAKE CHANGE ON
 SHEET P1.0, FIRE PROTECTION GENERAL NOTE B)
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722