| Plan Review Notes For Permit 06100955 |
| Permit Number |
06100955 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-20 15:16:41 | *****DENIED***** | | | | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEREOF. | | | | | | 3.INDICATE ON APPROPRIATE ELEVATION FRONT THE SUITE | | | NUMBER FOR THIS TENANT SPACE.BE ADVISED THAT THE | | | NUMBER IS TO BE VISIBLE BEFORE, DURING, AND AFTER | | | CONSTRUCTION/DEMOLITION OPERATIONS. | | | | | | 4.INTERIOR FINISH FOR WALLS AND CEILING SHALL BE | | | CLASS "A" OR CLASS "B". | | | | | | 5.IF THE FIRE SPRINKLER AND (OR) FIRE ALARM SYSTEM IS | | | TO BE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE PLANS | | | AND PERMIT ARE REQUIRED. | | | | | | 6.IN REGARDS TO FIRE SPRINKLER COVERAGE, NFPA 13 - | | | 2002 EDITION - SHALL BE REFERENCED.(MAKE CHANGE ON | | | SHEET P1.0, FIRE PROTECTION GENERAL NOTE B) | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE SHEET INDICATING HOW/WHERE EACH ITEM | | | WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|