Plan Review Notes
Plan Review Notes For Permit 06100955
Permit Number 06100955
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-01 14:26:06****** UNSAT ********
  
 1) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ARCHITECTURAL/ENGINEER FIRM AS
 REQUIRED UNDER FAC 61G1-16.004, FAC 61G15-23.002, FS
 481.219, AND FS471.023.
 PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS FIRM ON
 SEVERAL OCCASIONS ON OTHER PROJECTS. AT THIS TIME ONE
 SET OF PLANS ARE BEING RETAINED FOR POSSIBLE REVIEW
 FROM THE STATE'S LEGAL COUNSEL TO THE FLORIDA BOARD OF
 ARCHITECT'S.
 PLEASE ADDRESS THIS COMMON AND OBTAIN THE CORRECT
 LICENSURE AS REQUIRED.
 PLEASE ALSO SEE OTHER INFORMATION REQUIRED ON THE SAME
 SAID TITLE BLOCKS.
 ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S)>
  
 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE LISTED ON SAID PLANS.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, AND THE 2004
 FBC.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-101.1.3,
 13-415.1.ABC.1.1, .1.2 AND .1.3,
 PLEASE PROVIDE SCHEDULING FOR SYSTEM, PLEASE PROVIDE
 THE MAX TIMES FOR OVER RIDING DEVICES. (30MINS MAX ON
 OC SENSOR TYPE DEVICES, 4HRS MAX FOR TIME TYPE.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1, AND TABLES.
 ** PLEASE KNOW AT THIS TIME, A "SYSTEM" CAN NOT BE
 REVIEWED AS NONE WAS SHOWN OR SUBMITTED.
  
 4) NOTE: PLEASE SEE RISER WHICH SHOWS LINE AND LOAD IN
 THE SAME GUTTER.
 230.7 THIS IS NOT PERMITTED.
  
 5) NOTE: PLEASE SEE EQUIPMENT GROUNDING CONDUCTORS ARE
 NOT PERMITTED BEFORE THE FIRST MEANS OF DISCONNECT.
 250.6,250.24B
  
 6) NOTE: PLEASE KNOW, THAT RISER NOTES A AND B ARE NOT
 ON RISER AT THIS TIME?
 NOT COMPLETE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE 230.2, AN ADDITIONAL NEW SERVICE
 FROM FPL IS NOT GRANTED AT THIS TIME. PLEASE PROVIDE
 ALL INFORMATION AND DOCUMENTATION FOR REVIEW.
  
 8) NOTE: PLEASE SEE 250.66 FOR CORRECT SIZING OF THE
 GROUNDING ELECTRODE CONDUCTOR.
  
 9) NOTE: PLEASE SUBMIT AND SHOW COORDINATION WITH AIC
 RATINGS OF ALL EQUIPMENT AS SHOWN. THIS MAY CHANGED DUE
 TO POSSIBLE CHANGES IN SERVICE.
 110.9,240.12
  
 10) NOTE: PLEASE PROVIDE LOADS AND SHOW LOADS FOR TRACK
 LIGHTS PER 220.12B AND LOADS ON SHOW/DISPLAY WINDOWS
 PER 220.12A.
  
 11) NOTE: PLEASE SEE MINIMUM VA FOR SIGN CIRCUIT PER
 600.5, 220.3(B)(6).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-30 09:59:30REMOVED FROM INCOMING, IN ELECTRICAL FOR REVIEW.