| 2006-11-01 14:26:06 | ****** UNSAT ******** |
| | |
| | 1) NOTE: PLEASE SEE MISSING REQUIRED INFORMATION ON |
| | TITLE BLOCKS FOR ARCHITECTURAL/ENGINEER FIRM AS |
| | REQUIRED UNDER FAC 61G1-16.004, FAC 61G15-23.002, FS |
| | 481.219, AND FS471.023. |
| | PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS FIRM ON |
| | SEVERAL OCCASIONS ON OTHER PROJECTS. AT THIS TIME ONE |
| | SET OF PLANS ARE BEING RETAINED FOR POSSIBLE REVIEW |
| | FROM THE STATE'S LEGAL COUNSEL TO THE FLORIDA BOARD OF |
| | ARCHITECT'S. |
| | PLEASE ADDRESS THIS COMMON AND OBTAIN THE CORRECT |
| | LICENSURE AS REQUIRED. |
| | PLEASE ALSO SEE OTHER INFORMATION REQUIRED ON THE SAME |
| | SAID TITLE BLOCKS. |
| | ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S)> |
| | |
| | 2) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| | CODES ARE LISTED ON SAID PLANS. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, AND THE 2004 |
| | FBC. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13, 13-101.1.3, |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3, |
| | PLEASE PROVIDE SCHEDULING FOR SYSTEM, PLEASE PROVIDE |
| | THE MAX TIMES FOR OVER RIDING DEVICES. (30MINS MAX ON |
| | OC SENSOR TYPE DEVICES, 4HRS MAX FOR TIME TYPE. |
| | PLEASE SEE 13-415.2, 13-415.2.ABC.1, AND TABLES. |
| | ** PLEASE KNOW AT THIS TIME, A "SYSTEM" CAN NOT BE |
| | REVIEWED AS NONE WAS SHOWN OR SUBMITTED. |
| | |
| | 4) NOTE: PLEASE SEE RISER WHICH SHOWS LINE AND LOAD IN |
| | THE SAME GUTTER. |
| | 230.7 THIS IS NOT PERMITTED. |
| | |
| | 5) NOTE: PLEASE SEE EQUIPMENT GROUNDING CONDUCTORS ARE |
| | NOT PERMITTED BEFORE THE FIRST MEANS OF DISCONNECT. |
| | 250.6,250.24B |
| | |
| | 6) NOTE: PLEASE KNOW, THAT RISER NOTES A AND B ARE NOT |
| | ON RISER AT THIS TIME? |
| | NOT COMPLETE. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE 230.2, AN ADDITIONAL NEW SERVICE |
| | FROM FPL IS NOT GRANTED AT THIS TIME. PLEASE PROVIDE |
| | ALL INFORMATION AND DOCUMENTATION FOR REVIEW. |
| | |
| | 8) NOTE: PLEASE SEE 250.66 FOR CORRECT SIZING OF THE |
| | GROUNDING ELECTRODE CONDUCTOR. |
| | |
| | 9) NOTE: PLEASE SUBMIT AND SHOW COORDINATION WITH AIC |
| | RATINGS OF ALL EQUIPMENT AS SHOWN. THIS MAY CHANGED DUE |
| | TO POSSIBLE CHANGES IN SERVICE. |
| | 110.9,240.12 |
| | |
| | 10) NOTE: PLEASE PROVIDE LOADS AND SHOW LOADS FOR TRACK |
| | LIGHTS PER 220.12B AND LOADS ON SHOW/DISPLAY WINDOWS |
| | PER 220.12A. |
| | |
| | 11) NOTE: PLEASE SEE MINIMUM VA FOR SIGN CIRCUIT PER |
| | 600.5, 220.3(B)(6). |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-10-30 09:59:30 | REMOVED FROM INCOMING, IN ELECTRICAL FOR REVIEW. |