Plan Review Notes
Plan Review Notes For Permit 06100943
Permit Number 06100943
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-30 08:23:17 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  
 2} THE SERVICE ENTRANCE CONDUCTORS MUST COMPLY WITH
 310.15(B)(6) OR 310.16. MINIMUM 2/0 FOR 200 AMPS.
  
 3 } THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. MINIMUM #4 COPPER.
  
 4} ALL CODES REFERENCED ON THE PLANS ARE INCORRECT. THE
 CURRENT BUILDING CODE IS 2004, THERE IS NO MORE SBCCI
 CODES IN THE STATE OF FLORIDA. THE CURRENT NEC IS THE
 2002 EDITION . CORRECT ALL REFERENCES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.