Plan Review Notes
Plan Review Notes For Permit 06100906
Permit Number 06100906
Review Stop P
Sequence Number 1
Notes
Date Text
2006-11-18 14:36:22DENIED;
 PAGE A-3 SANITARY RISER DIAGRAM;
 1.AUTOMATIC CLOTHES WASHER TO DISCHARGE DOWN
 STREAM OF THE BATHROOM GROUP SEE FBC-2004 PLUMBING
 SECTION 909.1.
 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3"
 SECTION 406.3.
 3.CLEANOUT REQUIRED ON WASHER VENT 48" ABOVE
 FINISH FLOOR.
 PLUMBING PLAN REVIEW BY;