Plan Review Notes
Plan Review Notes For Permit 06100906
Permit Number 06100906
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-08 12:40:18 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 1} PROVIDE LOAD CALCULATIONS PER 220 SECTION I,
 STANDARD CALCULATION,IF DERATING THE NEUTRAL, OR
 220.SECTION III, OPTIONAL CALCULATIONS. THE TOTAL LOADS
 AFTER DEMAND APPEAR TO BE LARGER THAN THE SERVICE
 RATING.
  
 2}AN EGUIPMENT GROUND SIZEDPER 250.122 IS REQUIRED
 TO BE RAN WITH THE FEED FOR THE SUBPANEL. INDICATE SAME
 ON THE RISER.
  
 3}THE BATH CIRCUIT REQUIRED BY 210.11(C)(3), MUST
 APPEAR IN THE PANEL SCHEDULE.
  
 4}PLEASE INDICATE THE REQUIRED ARC FAULT CIRCUITS
 (210.12) IN THE PANEL SCHEDULE .
  
 5}A RECEPTACLE NEEDS TO BE ADDED TO THE PROPOSED
 BEDROOM FOR SPACING REQUIREMENTS OF 210.52(A)(1).
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.