| Notes |
| Date |
Text |
| 2006-11-08 12:40:18 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | INSPECTION. | | | | | | 1} PROVIDE LOAD CALCULATIONS PER 220 SECTION I, | | | STANDARD CALCULATION,IF DERATING THE NEUTRAL, OR | | | 220.SECTION III, OPTIONAL CALCULATIONS. THE TOTAL LOADS | | | AFTER DEMAND APPEAR TO BE LARGER THAN THE SERVICE | | | RATING. | | | | | | 2}AN EGUIPMENT GROUND SIZEDPER 250.122 IS REQUIRED | | | TO BE RAN WITH THE FEED FOR THE SUBPANEL. INDICATE SAME | | | ON THE RISER. | | | | | | 3}THE BATH CIRCUIT REQUIRED BY 210.11(C)(3), MUST | | | APPEAR IN THE PANEL SCHEDULE. | | | | | | 4}PLEASE INDICATE THE REQUIRED ARC FAULT CIRCUITS | | | (210.12) IN THE PANEL SCHEDULE . | | | | | | 5}A RECEPTACLE NEEDS TO BE ADDED TO THE PROPOSED | | | BEDROOM FOR SPACING REQUIREMENTS OF 210.52(A)(1). | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|