2007-01-08 11:29:05DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS
 REQUIRED BY FBC RESIDENTIAL R807.1.
  
 3) FBC R803.2.3.1 REQUIRES ROOF SHEATHING FASTENERS 4"
 O.C. IN ZONE 3, WHICH INCLUDES MORE THAN GABLE ENDS.
 PLEASE CORRECT NOTE ON A3.
  
 4) TWO LAYERS OF UNDERLAYMENT ARE REQUIRED ON ROOF
 SLOPES LESS THAN 4:12 PER R905.2.7. PLEASE CORRECT NOTE
 ON A3.
  
 5) SPECIFY 8D RING SHANK NAILS IN DETAIL 6/SD-1 AND
 2/SD-1 AS REQUIRED BY R803.2.3.1.
  
 6) ON SHEET SD-1 PLEASE UPDATE CODE REFERENCES TO THE
 2004 FBC, ASCE7-02, ACI 318-02, ACI 402-02 AND ACI
 630-02. SEE 2004 FBC AND REFERENCED STANDARDS.
  
 7) THE ENERGY CALC. FORMS ARE REQUIRED TO BE SIGNED BY
 THE OWNER/AGENT PER FBC CHAPTER 13.
  
 8) THE SOIL REPORT SPECIFIES AN ALLOWABLE BEARING
 PRESSURE OF 2000 PSF AND THE DESIGN ON S-1 REQUIRES A
 2500 PSF SOIL BEARING CAPACITY.
  
 9) THE TRUSS LAYOUT AND DRAWINGS ARE REQUIRED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 ADDITION.
  
 10) MOST OF THE UPLIFT VALUES SPECIFIED ON THE ROOF
 FRAMING PLAN ON S-1 ARE LESS THAN THOSE SHOWN THE TRUSS
 DRAWINGS, ALTHOUGH THE CAPACITIES OF THE SPECIFIED
 CONNECTORS ARE ADEQUATE.
  
 11) PLEASE CLARIFY THE ATTACHMENT OF THE GIRDER TRUSSES
 AT THE ENTRY PORCH TO THE COLUMNS ON S-1.
  
 12) ON S-1 AT THE REAR WALL OF THE PROPOSED FAMILY ROOM
 DETAIL 7/SD-1 IS SPECIFIED. THIS IS A NEW WALL AND
 IMBED CONNECTORS SHOULD BE SPECIFIED AT THIS LOCATION.
  
 13) GIRDER M1G HAS AN "E" CONNECTOR SPECIFIED AT THE
 NEW EXTERIOR WALL, HOWEVER THERE IS NO "E" CONNECTOR
 SPECIFIED IN THE CONNECTOR SCHEDULE.
  
 14)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE FRENCH DOOR AT
 REAR OF FAMILY ROOM.
  
 16) THE PRODUCT APPROVAL NOA FOR THE IMPACT RATED
 SINGLE HUNG WINDOWS IS EXPIRED PLEASE SUBMIT THE NEW
 ONE (06-0406.08).
  
 17) A PRODUCT APPROVAL FOR STORM SHUTTERS WAS
 SUBMITTED. PLEASE CLARIFY WHERE AND HOW THEY WILL BE
 INSTALLED. SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE
 INDICATE THE SPANS, FASTENERS, FASTENER SPACING,
 CONNECTION TYPE, EDGE DISTANCE, ETC. FOR EACH OPENING.
 THIS IS REQUIRED TO DETERMINE IF THE INSTALLATION WILL
 COMPLY WITH PRODUCT APPROVAL FOR THE PRESSURES AT THE
 OPENING.
  