| 2006-12-23 19:11:27 | **UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS |
| | STILL IN NEED OF ADDRESSING. |
| | PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW AND NOTED WITH AN OK, NO WITH FURTHER |
| | EXPLANATION. |
| | PLEASE SEE SOME MAY BE NOTED NO/OK WHICH WOULD INDICATE |
| | COMMENT WAS PARTIALLY ADDRESSED. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK, HOWEVER SEE WHITE-OUT ON PLANS WHICH IS |
| | NOT PERMITTED ON PLANS WHETHER OR NOT THEY ARE SIGNED |
| | AND SEALED BY AN ENGINEER OR ARCHITECT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR |
| | AUTOMATED LIGHTING CONTROL OF SOME TYPE REQUIRED. IF |
| | OCC SENSOR TYPE, PLEASE INDICATE MAX TIME OF 30MINS, IF |
| | TIMER TYPE, PLEASE INDICATE THE MAX OF 4HRS. |
| | |
| | 3) NOTE:NO, PLEASE SEE THE TABLE/BLOCK AS SHOWN DOES |
| | NOT CORRELATE. PLEASE SEE THE FIRST THING IS IF USING |
| | THE SPACE BY SPACE IN TABLE B, THEN PLEASE SEE AREAS |
| | SHALL BE BROKEN DOWN FOR USE. PLEASE SEE ALL MAY NOT BE |
| | ONLY SHOWN AS OFFICE, UNLESS ALL IS ONE OPEN OFFICE |
| | SPACE OR IF ALL ARE INDEED OFFICES. |
| | PLEASE SEE THE MAX LPD AS SHOWN DOES NOT CORRELATE. |
| | PLEASE SEE 1.1 TIMES(X) THE SQ FT OF1450 IS NOT 1600. |
| | (MAY NOT ROUND UP) |
| | PLEASE SEE THE FIXTURE WATTAGE DOES NOT CORRELATE TO |
| | THE FIXTURE LEGEND. PLEASE SEE EVEN IF FIXTURES WERE |
| | 58WATTS EACH, 58 TIMES 30 IS 1740 WHICH EXCEEDS THE |
| | ALLOWANCE EVEN AS SHOWN. |
| | PLEASE SEE WATTAGE ON EACH FIXTURE IS 64, OR AT LEAST |
| | BY THE INFORMATION AS SHOWN ON FIXTURE LEGEND WHICH |
| | WOULD PLACE THE WATTAGE AT 1920. |
| | PLEASE ADJUST AND SEE TABLE B. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE MAX WATTAGE(LIGHTING POWER |
| | DENSITIES ) PER 13.415.2.ABC.1, (OFFICE, ETC SPACE.) |
| | CAN BE SHOWN ON A BLOCK ON PLANS. |
| | |
| | 4) NOTE: OK. |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE CLARIFY IF THE CONTINUOUS LOADS ARE |
| | SHOWN AT 125%. 215.3, 230.42 |
| | THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |