| Plan Review Notes For Permit 06100894 |
| Permit Number |
06100894 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-20 12:09:09 | ****UNSAT**** | | | | | | | | | | | | 1.FLORIDA FIRE PREVENTION CODE 2004 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.SINCE THE SCOPE OF THE WORK WILL REQUIRE | | | MODIFICATION OF THE FIRE PROTECTION SYSTEM(S), SEPARATE | | | PERMITS AND PLANS WILL BE REQUIRED. | | | | | | 4.AS PER WPB FIRE PREVENTION, DUCT DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM.(MAKE CHANGE TO FIRE | | | ALARM NOTE #17, SHEET FA 0.1) | | | | | | 5.CORRECT SPELLING OF "FIRE" ON SHEET FA2.1, KEY NOTE | | | #2. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|