| Date |
Text |
| 2007-11-02 16:45:15 | ** PLANS WERE REMOVED FROM INCOMING. PLANS ROUTED TO |
| | BUILDING REVIEWER AFTER ELECTRICAL REVIEW WSA |
| | COMPLETED. PLANS WILL BE PLACED ON THE COMM BOARD AFTER |
| | BUILDING REVIEW. |
| 2007-11-02 16:44:10 | |
| | ** DENIED 4TH REVIEW ** |
| | |
| | *** PLEASE SEE AS THE ENERGY CALCULATIONS WERE NOT |
| | SUBMITTED ON THE PREVIOUS REVIEW AS STATED IN NOTE # 2 |
| | DATED 6/4/07 A REVIEW ON THE ENERGY CALCULATIONS WERE |
| | NOT ABLE TO BE DONE UNTIL THIS REVIEW. |
| | REVIEW OF OTHER PREVIOUS CODE COMMENTS WAS DONE. |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS |
| | SUBMITTED ARE IN NEED OF COMPLIANCE WITH THE FBC |
| | CHAPTER 13. |
| | PLEASE SEE THE VERSION AS NOW SUBMITTED IS INCORRECT |
| | FOR THE PERMIT APPLIED DATE. THIS PROJECT WAS SUBMITTED |
| | UNDER THE 2004 FBC BEFORE THE DECEMBER 8TH, 2006 |
| | CHANGES THEREFORE THE VERSION AS ADOPTED SHOULD BE |
| | 2.11. |
| | 13-415.1.A, 13- 400.3.A |
| | PLEASE SEE THAT THE INFORMATION ON THE INPUT DATA |
| | REPORT DOES NOT CORRELATE WITH LIGHTING AS SHOWN ON |
| | PLANS. ANY REFERENCE TO THE INPUT DATA REPORT ON THE |
| | COMMENT AS NOTED WILL BE ABBREVIATED AS IDR. |
| | PLEASE SEE THE AMOUNT OF FIXTURES AND WATTAGES OF |
| | FIXTURES ON THE IDR DO NOT MATCH WITH THE FIXTURES ON |
| | PLANS. |
| | FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING FIXTURES |
| | WHICH ON PLANS ACTUALLY SHOW MORE FIXTURES THAN IN |
| | CALCULATIONS. SEE THAT FIXTURE *C* IS ACTUALLY |
| | MISSING. |
| | PLEASE SEE THE INTERIOR LIGHTING AS THERE IS FIXTURES |
| | ON PLANS WHICH ARE NOT IN THE IDR. FOR EXAMPLE: |
| | FIXTURES H, H1, J, L ARE NOT IN THE IDR. FIXTURE H, IS |
| | SHOWN AS 1005 WATTS ON THE LIGHTING FIXTURE SCHEDULE |
| | WHICH APPEARS TO BE A MISPRINT. PLEASE SEE THE IDR AS |
| | THESE FIXTURES ABOVE WHICH ARE 75W AND 100W FIXTURES |
| | ARE NOT LISTED AT ALL. |
| | PLEASE SEE THE NUMBER OF FIXTURES IN ROOMS AND OTHER |
| | AREAS ARE MISSING. FOR EXAMPLE: WHERE ARE THE FIXTURES |
| | *H* IN THE IDR? |
| | |
| | ** THESE ARE SOME EXAMPLES GIVEN. |
| | PLEASE COORDINATE ALL LIGHTING ON PLANS AND FIXTURE |
| | SCHEDULE WITH THE ENERGY CALCULATIONS AND THE INPUT |
| | DATA REPORTS. |
| | ** PLEASE SEE THE OWNER AGENT WILL NEED TO SIGN THE |
| | CERTIFICATION SHEET ALSO. |
| | |
| | 2) NOTE: PLEASE KNOW AS THE ENERGY CALCULATIONS WERE |
| | NOT SUBMITTED PREVIOUSLY FS 553.80(2)(B) DOES NOT APPLY |
| | AT THIS TIME. PLEASE BE SURE TO COORDINATE. |
| | ** PLEASE KNOW THAT ONE SET OF ELECTRICAL PLANS AND ONE |
| | SET OF ENERGY CALCULATIONS ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | WHEN RESUBMITTING PLANS PLEASE BE SURE TO INCLUDE ONE |
| | NEW ELECTRICAL SET IN THE THIRD SET OF PLANS. |
| | ** IF ANY ELECTRICAL SHEETS ARE BEING REPLACED IN OTHER |
| | TWO SETS DUE TO NOTES ABOVE, PLEASE REMOVE OLD/VOIDED |
| | SHEETS AND INSERT NEW SHEETS INTO SETS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |