| 2006-12-14 20:44:09 | *****DENIED***** |
| | |
| | |
| | |
| | 1.ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF 20 |
| | FT AND AN UNOBSTRUCTED VERTICAL CLEARANCE OF 13FT 6IN. |
| | THE ROADS SHALL ALSO BE DESIGNED AND MAINTAINED TO |
| | SUPPORT 32 TONS OF FIRE APPARATUS. |
| | |
| | 2. WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE |
| | PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN |
| | SERVICE PRIOR TO CONSTRUCTION WORK. |
| | |
| | 3.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR |
| | HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY |
| | THEROF. |
| | |
| | 4.LANSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| | FIRE PROTECTION EQUIPMENT.PROPER CLEARANCES SHALL BE |
| | MAINTAINED AT ALL TIMES. |
| | |
| | 5.PANIC HARDWARE OR FIRE EXIT PANIC HARDWARE REQUIRED |
| | ON ALL EXIT DOORS THAT HAVE AN OCCUPANT LOAD OF 100 OR |
| | MORE PERSONS TRAVELING THROUGH THEM. |
| | |
| | 6.FIRE EXTINGUISHERS TO BE 2A:10 BC RATED. |
| | |
| | 7.THE FIRE ALARM SYSTEM IN CONJUNCTION WITH THE FIRE |
| | SPRINKLER SYSTEM SHALL MEET THE REQUIREMENTS OF BEING |
| | MONITORED BY A LICENSED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 8.KNOX BOX FOR THE BUILDING WILL BE REQUIRED. |
| | |
| | 9.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING |
| | ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE, |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN |
| | WIDTH CONTRASTING TO THEIR BACKGROUND. |
| | |
| | 10. FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80. |
| | |
| | 11. PROVIDE LAYOUT OF THE FIRE SPRINKLER AND FIRE ALARM |
| | SYSTEM FOR THE BUILDING.A SEPARATE PERMIT AND PLAN |
| | WILL BE REQUIRED FOR EACH. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |