| 2006-11-05 18:34:24 | *** UNSAT *** |
| | |
| | ** PLEASE SEE SOME OF THE COMMENTS BELOW DO NO PERTAIN |
| | TO JLRD ENGINEERING AND ARE BEING NOTED AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE ADDRESS ON PLANS STATES 2700 NORTH |
| | MILITARY TRAIL, YET PLEASE SEE COMMENTS FROM THE |
| | ADDRESSING REVIEWER. |
| | PLEASE KNOW ONCE AN ADDRESS IS OBTAINED AND FINALIZED |
| | PLEASE BE SURE TO PLACE ON ALL TITLE BLOCKS AS |
| | REQUIRED. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE SOME SURVEY/ SITE SHEETS ARE NOT |
| | SIGNED AND SEALED. SEEMS SOME WERE MISSED. FS 472.025 |
| | |
| | 3) NOTE: PLEASE SEE "C" SHEETS, ARE ALSO NOT SIGNED, |
| | DATED OR SEALED. PLEASE SEE COMMENTS FROM ENGINEERING |
| | REVIEWER. FS 481/471 |
| | |
| | 4) NOTE: PLEASE SEE MINIMUM SIZE SEAL REQUIRED FOR |
| | LANDSCAPE ARCHITECT PER FAC 61G1-16.002. *THIS IS ONLY |
| | NOTED BY THIS REVIEWER* |
| | |
| | 5) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WILL |
| | BE REQUIRED TO BE SIGNED, DATED AND SEALED BY THE |
| | RESPONSIBLE DESIGNER ONCE REVISED. PLEASE SEE THE SETS |
| | SUBMITTED WERE NOT DONE. |
| | PLEASE ALSO SEE FUTURE COMMENTS WITH RESPECT TO FBC |
| | 2004 CHAPTER 13. |
| | |
| | 6) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING CODES AT A |
| | MINIMUM ARE STATED ON PLANS WHICH ARE RELEVANT TO THE |
| | DESIGN OF PLANS SUBMITTED. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, AND 2004 |
| | FBC. |
| | |
| | 7) NOTE: PLEASE SEE ACCESS TO THE MAIN ELECTRICAL ROOM |
| | TO SHUT OFF POWER IN AN EMERGENCY AS SHOWN IS NOT |
| | PERMITTED. PLEASE SEE ACCESS TO THE MAIN ELECTRICAL |
| | ROOM IS MOST IMPORTANT IF THE FIRE DEPT PERSONNEL ARE |
| | IN NEED OF SHUTTING DOWN POWER. |
| | PLEASE SEE ONCE OBTAINING ENTRANCE INTO THE BUILDING |
| | WHICH COULD BE LOCKED, PLEASE SEE PLANS SHOW A TRAVEL |
| | DISTANCE DOWN A HALLWAY, THROUGH ANOTHER POSSIBLE |
| | LOCKED DOOR, THROUGH A STORAGE ROOM AND ANOTHER LOCKED |
| | DOOR. |
| | PLEASE KNOW THE SCENARIO AS SHOWN IS NOT ACCEPTABLE TO |
| | THIS AHJ AND IS A LIFE SAFETY ISSUE TO THIS OFFICE. |
| | PLEASE SEE 100, 230.70, 230.71. |
| | IT IS OF THE UTMOST IMPORTANCE TO PROVIDE ACCESS |
| | DIRECTLY FROM THE OUTSIDE WITH A POSSIBLE "KNOX BOX" |
| | WILL BE REQUIRED. THIS LOCATION OF A DOOR POSSIBLY AT |
| | THE REAR OF BLDG AND "KNOX BOX" LOCATION SHALL BE |
| | DETERMINED BY THE FIRE MARSHAL'S OFFICE IN COORDINATION |
| | WITH THE ELECTRICAL REVIEW COMMENTS. |
| | |
| | 8) NOTE: PLEASE PROVIDE WIND LOAD CALCULATIONS FOR |
| | LIGHT POLES WITH THE (EPA) EFFECTIVE PROJECTED AREA OF |
| | THE LIGHT FIXTURES FIGURED IN WITH THE CALCULATIONS. |
| | THESE ARE REQUIRED TO BE DONE AT THIS TIME BY A FLORIDA |
| | REGISTERED PE. PLEASE KNOW THIS WILL BE REVIEWED BY THE |
| | STRUCTURAL REVIEWER FOR COMPLIANCE WITH THE 140MPH 3SEC |
| | GUST/ 120 SUSTAINED WIND LOADS. |
| | 9) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR |
| | THE BRANCH CIRCUITS FOR SITE LIGHTING. |
| | PLEASE ALSO PROVIDE FOR A WORST CASE FOR OTHER BRANCH |
| | CIRCUITS. |
| | 13-413.1.ABC.1.2 |
| | |
| | 10) NOTE: PLEASE SEE 2004 FBC CHAPTER 13. |
| | A) PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. |
| | B) PLEASE SHOW A DETAILED SYSTEM WHICH IS REQUIRED. C) |
| | PLEASE PROVIDE SCHEDULING OF SYSTEM. |
| | D) PLEASE PROVIDE ALL OVER RIDE DEVICES AT THE |
| | LOCATIONS FOR THE OCCUPANTS TO OVER RIDE SYSTEM, THESE |
| | DEVICES ARE REQUIRED TO BE LOCATED SO THE OCCUPANT CAN |
| | VISUALLY SEE THE LIGHTING BEING CONTROLLED. |
| | E) PLEASE PROVIDE ALL TIMES FOR OVER RIDE DEVICES. |
| | (30MINS MAX FOR OCC SENSOR TYPE DEVICES AND 4HRS MAX |
| | FOR TIMER TYPE DEVICES). |
| | F) PLEASE SEE ALL SPACES, AND ROOMS WHICH CONTAIN FLOOR |
| | TO CEILING HEIGHT PARTITIONS SHALL ALL CONTAIN OVER |
| | RIDE DEVICES OF SOME SORT WHICH WILL AUTOMATICALLY SHUT |
| | OFF LIGHTING ON THOSE AREAS. (OFFICES, STORAGE ROOMS, |
| | CONFERENCE ROOMS, ETC) |
| | G) PLEASE SEE 13-415.1.AB.1, 13-415.1.A, IF USING |
| | METHOD "A", PLEASE SEE AS SUBMITTED ALL ARE SHOWN A |
| | MANUAL ON/OFF, WHICH WOULD CHANGE TO AUTO. |
| | PLEASE ALSO SEE 13-415.2 |
| | H) PLEASE SEE AREAS GREATER THAN 10K SQ FT. |
| | 13-415.1.ABC.1.2, PLEASE SEE AREAS LARGER THAN 25K SQ |
| | FT 13-415.1.ABC.1.1 |
| | |
| | 11) NOTE: PLEASE INDICATE THE GROUNDING ELECTRODE |
| | ATTACHMENT LOCATIONS FOR THE SD TRANSFORMERS.250.30, |
| | 250.20, 250.66 |
| | PLEASE SHOW. |
| | |
| | 12) NOTE: PLEASE EXPLAIN THE ONSITE CUSTOMER OWNED |
| | 13.2KV SYSTEM? HOW IS THIS NOT FPL / UTILITY POWER FROM |
| | SOMEWHERE ARE DOWN THE LINE? |
| | PLEASE CLARIFY. |
| | IF INDEED, THIS IS AN ADDITIONAL SD SYSTEM, PLEASE |
| | DETAIL THE GROUNDING ELECTRODE. |
| | PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THIS |
| | TRANSFORMER UNIT WHICH INDICATES OCP AND A |
| | TRANSFER/SWITCH? IS THIS INSIDE OR OUTSIDE THIS |
| | TRANSFORMER? |
| | PLEASE SEE THIS TRANSFORMER SEEMS TO ALSO INDICATE A |
| | GROUND? IS THIS BONDED AT THIS LOCATION AND THEN BONDED |
| | AGAIN AT THE HDP? 250.6, 250.24B. |
| | 230.70, 230.76, 230.79, 250.30, ETC |
| | PLEASE KNOW AT THIS POINT THERE ARE MANY QUESTIONS ON |
| | THIS SYSTEM AS SHOWN? |
| | |
| | 13) NOTE: PLEASE SEE HDP IS BEING SHOWN ON SCHEDULE |
| | WITH "GFI" PROTECTION, HOWEVER PLEASE SEE 240.13, |
| | 230.95, THIS WOULD BE "GF" PROTECTION AS "GFI" IS FOR |
| | PERSONNEL PROTECTION. |
| | |
| | 14) NOTE: PLEASE SUBMIT LOAD CALCULATIONS, LOAD |
| | SUMMARY. PLEASE SEE NEC 220., 220.3, 220.10, 220.11, |
| | 220.13 ETC. |
| | PLEASE INDICATE AND SHOW ALL CONTINUOUS LOADS AT 125%, |
| | 215.3, 230.42. |
| | FBC ADMIN SECT 106.1.2, 106.3.5.1.2 AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 15) NOTE: PLEASE INDICATE ALL DEVICE LEVELS FOR ADA |
| | REQUIREMENTS IN CHAPTER 11 OF THE 2004 FBC. |
| | PLEASE SEE 11-4.28.1, 11-4.28.2, AND 11-4.28.3(4). |
| | PLEASE INDICATE THE MINIMUM DECIBEL LEVELS AND THE MIN |
| | OF 75 CANDELAS FOR STROBE/VISUAL DEVICES. PLEASE KNOW |
| | THIS IS MORE RESTRICTIVE THAN NFPA-72 AND WILL BE |
| | REQUIRED. |
| | |
| | |
| | ** PLEASE KNOW AS A "SYSTEM" FOR CHAPTER 13 IS NOT YET |
| | SUBMITTED, THERE MAY BE FURTHER COMMENTS. |
| | |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-11-05 16:58:25 | IN ELEC FOR REVIEW |