Plan Review Notes
Plan Review Notes For Permit 06100890
Permit Number 06100890
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-14 10:48:24BUILDING REVIEW CHECKLIST:
  
 1- CLARIFY INFORMATION GIVEN IN THE INSTALLATION
 SCHEDULE:
 A) NUMBER OF OPENINGS SHOWN ON APARTMENT LAYOUT
 DON'TMATCH NUMBER OF OPENINGS SHOWN ON THE
 INSTALLATION SCHEDULE.
 B) IS NOT CLEAR WHICH OPENING IS GOING TO BE USED
 FOR EMERGENCY ESCAPE AND HOW IS IT COMPLYING WITHSEC.
 R310.4 2004 RESIDENTIAL CODE.
 C) CLARIFY SIZE OF OPENING AND SIZE OF SHUTTER SPAN.
 SIZES SHOWN ON INSTALLATION SCHEDULE DON'T WORK.
 D) WHERE ARE THE DESIGN PRESSURES TAKEN FROM? . THEY
 DON'T REFLECT REAL DESIGN PRESSURES. SEE TABLE 1609.6B
 2004 FBC 2004 OR TABLES IN ASCE 7-02.
 E) WHAT IS 1"BO INDICATED IN THE SHUTTERS MOUNTING
 AND CONNECTION TYPE COLUMN?. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 F) CLEARLY SPECIFY THE MINIMUM EDGE DISTANCE
 CONSIDERED FOR INSTALLATION.
 G) CLEARLY SPECIFY ANCHOR TYPE. THERE ARE SEVERAL
 TYPES OF TAPCONS WITH DIFFERENT DESIGN PRESSURES
 CAPACITY.
 H) CLEARLY SPECIFY SUBSTRATE TO BE ATTACHED TO:
 CONCRETE, CONCRETE BLOCK OR WOOD TO VERIFY COMPLIANCE
 WITH PROPOSED CONNECTOR INSTALLATION.
 I) STATEWIDE FLORIDA PRODUCT APPROVAL THAT
 CORRESPONDS TO SUBMITTED DRAWINGS IS FL2249(SEE
 ATTACHED COPY) NOT SSTD 12-99.REVISE AS REQUIRED.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712