| Plan Review Notes For Permit 06100878 |
| Permit Number |
06100878 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-26 15:03:02 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | | REVIEW PER 106.1 FBC AS AMENDED. INDICATE THE LOCATION | | | OF THE SERVICE EQUIPMENT BEING REFED, SHOW THE | | | DISCONNECT LOCATION. | | | | | | 2} INDICATE THE RATING OF THE EXISTING SERVICE. 215.5 | | | NEC. | | | | | | 3} SUBMIT A SITE PLAN SHOWING THE ROUTING OF THE | | | UNDERGROUND CONDUITS FROM FPL POLE TO THE METER. | | | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|