2006-11-02 11:46:58****CORRECTIONS****
 MYRON JACOBS BUILDING PLANS EXAMINER
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 _XX__ 1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 _XX__2.PROVIDE BUILDING HEIGHT.DESIGN PRESSURES
 FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7-02, FBC1609.1.1. DOCUMENTSPREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED SEALED ORIGINALS FAC61G15-23.002.
  
 _XX__3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX__4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE REQUIRED INFORMATION IN A SIMILAR FORMAT.
  
 ____ 5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 _XX__6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB. PAGE 9-11 NEED TO BE
 COMPLETED. INDICATE THE FASTENER
 SPACING.
  
 _XX__7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.SUBMIT A COMPLETE FLOOR PLAN SHOWING
 THE ENERGENCY ESCAPE.BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 SCALE UPON
 SUBSTANTIAL PAPER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  