| Plan Review Notes For Permit 06100861 |
| Permit Number |
06100861 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-02 09:48:07 | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | | REVIEW PER 106.1 FBC AS AMENDED. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | 3} INDICATE THE CORRECT CONDUIT AND CONDUCTOR SIZE AND | | | TYPE ON THE PLAN.SEE 250.122, MINIMUM 3/0 EQUIPMENT | | | GROUND, AND IN EACH PARALLEL RUN PER 250.122(F)(1). | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 |
|