| Date |
Text |
| 2006-10-30 14:48:21 | UNSAT |
| | REFERENCE: FBC-2004 PLUMBING, FBC-2004 CHAPTER 1 |
| | ADMINISRTRATIVE, FBC-2004 CHAPTER 11 FLORIDA |
| | ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION. |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED FOR PLUMBING PLAN |
| | REVIEW: |
| | |
| | 1. ALL TOILET ROOMS SHALL BE ACCESSIBLE: SUBMIT A |
| | FLOOR PLAN DETAIL AND AN ELEVATION DETAIL SHOWING |
| | COMPLIANCE WITH FBC-2004 CHAPTER 11 FLORIDA |
| | ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION, SECTIONS |
| | 11-4.16, 11-4.19 AND 11-4.22 AND ALL SUBSECTIONS. |
| | |
| | 2. PER FBC-2004 PLUMBING, TABLE 403.1. A MINIMUM OF |
| | ONE (1) SERVICE SINK REQUIRED FOR THE BUILDING. WITH |
| | THE CONVERSION OF THE FIFTH AND SIXTH FLOOR MOP SINKS |
| | TO WATER CLOSETS. PLEASE SHOW THAT THEBUILDING IS IN |
| | COMPLIANCE. |
| | |
| | 3. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.1.3 |
| | PLUMBING: |
| | (A) SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM |
| | INDICATING ALL WASTE, VENTS, AND TRAPS WITH SIZES FOR |
| | THE PROPOSED FIFTH AND SIXTH FLOOR STAFF BATHROOMS. |
| | (B) SUBMIT A WATER ISOMETRIC OF THE PROPOSED STAFF |
| | BATHROOMS WITH SIZES, SHUT OFF VALVES, WATER HAMMER |
| | ARRESTORS AND PLEASE INDICATE A POINT OF TIE INTO THE |
| | EXISTING POTABLE WATER SYSTEM WITH SIZING. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED AND |
| | PROVIDE ONE COPY OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K. STEVENS |
| | (561) 805-6721 |