| Notes |
| Date |
Text |
| 2007-05-25 14:02:55 | | | | | | | REVISION DENIED/INCOMPLETE INFORMATION. | | | | | | 1} PLEASE CORRECT THE PANEL SCHEDULE. THE REQUIRED BATH | | | CIRCUITS HAVE BEEN REMOVED, THERE IS NO DISHWASHER, | | | DISPOSAL OR LIGHTING CIRCUITS SHOWN. SEE PERMITTED | | | PLANS, USE THE SAME FORMAT. | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). SEE MASTER BATH NEEDS ADDED | | | RECEPTACLE. | | | | | | 3} THE DEMAND CALCULATION FOR THEAHU @100%=3150 AND | | | HTR@65%, IS INCORRECT. THE HEAT LOAD IS IN THE AHU, AND | | | 8000 WATTS IS NOT 65% OF ANY COMMON SYSTEM ON THE | | | MARKRT. THE PERMITTED SET OF MECHANICAL PLANS INDICATE | | | A 8000 WATT AHU. SEE NOTE #7 OF THE PREVIOUS REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|