Plan Review Notes
Plan Review Notes For Permit 06100844
Permit Number 06100844
Review Stop E
Sequence Number 5
Notes
Date Text
2007-05-25 14:02:55 
  
 REVISION DENIED/INCOMPLETE INFORMATION.
  
 1} PLEASE CORRECT THE PANEL SCHEDULE. THE REQUIRED BATH
 CIRCUITS HAVE BEEN REMOVED, THERE IS NO DISHWASHER,
 DISPOSAL OR LIGHTING CIRCUITS SHOWN. SEE PERMITTED
 PLANS, USE THE SAME FORMAT.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). SEE MASTER BATH NEEDS ADDED
 RECEPTACLE.
  
 3} THE DEMAND CALCULATION FOR THEAHU @100%=3150 AND
 HTR@65%, IS INCORRECT. THE HEAT LOAD IS IN THE AHU, AND
 8000 WATTS IS NOT 65% OF ANY COMMON SYSTEM ON THE
 MARKRT. THE PERMITTED SET OF MECHANICAL PLANS INDICATE
 A 8000 WATT AHU. SEE NOTE #7 OF THE PREVIOUS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  