Plan Review Notes
Plan Review Notes For Permit 06100844
Permit Number 06100844
Review Stop E
Sequence Number 4
Notes
Date Text
2007-05-16 15:12:55** UNSAT**
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 ** PLEASE SEE THE ELECTRICAL PLANS AND RISER DIAGRAM
 HAS BEEN REVISED FROM PREVIOUS REVIEWED PLANS WHICH
 HAVE CREATED NEW COMMENTS.
  
 1) NOTE: PLEASE SEE PLANS ARE NOT INDICATING ANY
 REVISIONS BY CLOUDS/TRIANGLES OR DATES IN TITLE BLOCK.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE MISSING AIC RATING FOR NEW MAIN.
 110.9
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE THE RISER DIAGRAM IS NOW REVISED
 SHOWING NEW MAIN, YET PLANS STILL INDICATE NO MAIN
 DISCONNECT OUTSIDE?
 PLEASE ALSO SEE THE SERVICE WAS REVISED ON THE PREVIOUS
 PLANS AND RISER TO INDICATE A 200A SERVICE HOWEVER THE
 PANEL SCHEDULE NOW SHOWS PANEL AT 150AMPS??
 PLEASE REVISE TO SHOW LOCATION OF ALL SERVICE EQUIPMENT
 ON PLANS.
 110.26, FBC 106.1.2
  
 4) NOTE: PLEASE SEE 250.6, 250.24 AS THE RISER IS
 MISSING THE EQUIPMENT GROUNDING CONDUCTOR FROM MAIN TO
 THE PANEL.
 * EQUIPMENT GROUNDS ARE INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT*
  
 5) NOTE: PLEASE SEE PLANS ARE MISSING THE RECEPTACLE
 OUTLET FOR DISHWASHER. ONLY THE COUNTER SPACE
 RECEPTACLE REQUIRED PER 210.52C IS SHOWN.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE GFI WHICH IS BEING SHOWN
 DIRECTLY BEHIND THE SINK WHICH IS NOT PERMITTED. THIS
 WAS REDLINED ON PREVIOUS PLANS; HOWEVER IT IS STILL
 BEING SHOWN AT THE SAME LOCATION.
 210.52C
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT
 CORRELATE THE LOADS ON PANEL SCHEDULE WITH THAT OF THE
 LOAD ON LOAD CALCULATIONS FOR THE AHU/A/C SYSTEM.
 PLEASE SEE THE MECHANICAL PLANS ON FILE ALSO DO NOT
 COORDINATE WITH EITHER OF THESE TWO AS SHOWN.
 PLEASE COORDINATE AND REVISED.
 PLEASE SEE 220, 424.
 FBC106.1.2
  
 8) NOTE: PLEASE SEE MISSING RECEPTACLE FOR WALL SPACE
 IN BREAKFAST/KITCHEN/DINING AREA.
 250.10
  
 9) NOTE: PLEASE SEE THE PANEL SCHEDULE SHOWS A NEW
 MICROWAVE CIRCUIT IN THE SPACE OF A SPARE AND PLANS DO
 NOT INDICATE CONDUCTORS, OCP, OR LOADS.
 PLEASE REVISED ALL AND CORRELATE.
 FBC 106.1.2
 310.16, 240.4, 408.4
  
 10) NOTE: PLEASE SEE PLANS DO CONTAIN A NOTE FOR WATER
 HEATER TO BE HARDWIRED HOWEVER THE PLANS STILL INDICATE
 A RECEPTACLE FOR THIS.
 PLEASE SEE 422.31, 422.30
  
 11) NOTE: PLEASE SEE PANEL SCHEDULE MUST BE REVISED FOR
 ALL CIRCUITS TO BE SPECIFIC TO ALL ROOMS AND AREAS IN
 WHICH THEY FEED. THE USE OF *GENERAL LIGHTS* IS NOT
 PERMITTED PER 408.4.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]